11 Installation Instruction

11.1. Select The Best Location

11.1.1. Indoor Unit
• Do not install the unit in excessive oil fume area such as
kitchen, workshop and etc.
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
11.1.2. Outdoor Unit
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over 7.5 m, additional refrigerant should be
added as shown in the table.
Piping size Rated
Length
Model
(m)
Gas Liquid
PC36HKV 3/4"
3/8"
5
Example: For PC36HKV
If the unit is installed at a 10m distance, the quantity of
additional refrigerant should 75 g ...... (10 - 7.5) m x 40 g/m =
100 g
Max.
Min.
Max.
Additional
Elevation
Piping
Piping
Refrigerant
(m)
Length
Length
(m)
(m)
20
3
30
11.2. Indoor/Outdoor Unit
Installation Diagram
(g/m)
40
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
19