11 Installation Instruction

11.1. Select the Best Location

11.1.1. Indoor Unit
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
11.1.2. Outdoor Unit
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over 7.5m, additional refrigerant should be
added as shown in the table.
Piping size Rated
Length
Model
Gas Liquid
(m)
C18HKF 1/2"
1/4"
5
C24HKF 5/8"
1/4"
5
Example: For C24HKF
If the unit is installed at a 10m distance, the quantity of
additional refrigerant should be 75g ...... (10 - 7.5)m x 30g/m =
75g
Max
Min.
Max.
Additional
Elevation
Piping
Piping
Refrigerant
(m)
Length
Length
(m)
(m)
20
3
25
20
3
25
11.1.3. Indoor/Outdoor
Diagram
(g/m)
20
30
22
Unit
Installation