TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
■ CONNECTION DIAGRAM
RT+
Close to terminate*
RT–
Shielded Twisted-pair
SD
Cable
To Other
T2
T-Link
+
T1
Devices
1
+
RUN
RUN CONTACT OUTPUT
4
RUN
2
U (+)
**
POWER INPUT
3
V (–)
**
6
FG
JACK
CONFIGURATION JACK
* When the module is at an end of the transmission line via
twisted-pair cable (= when there is no cross wiring), close
across the RT+ and RT– terminals with the jumper included
in the product package. Remove the jumper for all other locations.
**Not provided with 'No Power Supply' type module.
Caution: FG terminal is NOT a protective conductor terminal.
10 (.39)
27.5 (1.08)
6–M3
SCREW
1
4
2
5
3
TERMINAL
6
COVER
INTERNAL BUS
INTERNAL POWER
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
109 (4.29)

WIRING INSTRUCTIONS

■ M3 SCREW TERMINAL (power input, RUN contact output)
Torque: 0.5 N·m
■ SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.75 to 1.25 mm
3max
4min
12max
■ EURO TYPE CONNECTOR TERMINAL (T-Link)
Applicable wire size: 0.2 to 2.5 mm
Stripped length: 7 mm
R3-NF3
POSITIONING
GUIDE
2
3.2 dia.
(mm)
(AWG24 to 12)
2
EM-8288 Rev.2 P. 4 / 8