Download Print this page

Component Identification - M-system R3-NF3 Instruction Manual

T-link interface module

Advertisement

COMPONENT IDENTIFICATION

■ FRONT VIEW
SA1
SA2
RUN LED
ERR LED
Configuration Jack
Euro Type
Connector Terminal
1
4
2
5
3
6
■ FRONT ROTARY SW
• Node Address: SA1, SA2
Node Address is set in decimal. (Setpoint adjustment: 00 – 99)
■ FRONT DIP SW
(*)Factory Setting
• I/O Points setting: KS0, KS1
SW
DIGITAL: 16 POINTS
ANALOG: 4 POINTS
KS0
OFF (*)
KS1
OFF (*)
• Data setting: KS2
SW
DIGITAL
KS2
OFF (*)
• I/O Module Status setting: KS3
SW
I/O MODULE STATUS
WITHOUT
KS3
OFF (*)
• I/O Type setting: KS4, KS5
SW
I/O
KS4
OFF (*)
KS5
OFF (*)
• Analog Data Type setting: KS6, KS7
SW
16 BITS BINARY
KS6
OFF (*)
KS7
OFF (*)
■ SIDE VIEW
Node Address Setting
Rotary SW (MSB)
Node Address Setting
Rotary SW (LSB)
Network
RT+
RT–
SD
SW6
T2
8:KS7
T1
7:KS6
6:KS5
5:KS4
4:KS3
3:KS2
2:KS1
1:KS0
ON
DIGITAL: 32 POINTS
ANALOG: 8 POINTS
ON
OFF
DATA
ANALOG
ON
WITH
ON
OUTPUT
ON
OFF
ANALOG DATA TYPE
16 BITS BCD
ON
OFF
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
I/O POINTS
DIGITAL: 64 POINTS
ANALOG: 16 POINTS
OFF
ON
I/O TYPE
INPUT
OFF
ON
32 BITS BCD
OFF
ON
R3-NF3
DIP SW
SW3
SW2
SW1
4
8
8
3
7
7
2
6
6
1
5
5
4
4
ON
3
3
2
2
1
1
ON
ON
DIGITAL: 256 POINTS
ANALOG: 64 POINTS
ON
ON
I/O MODULE SPECIFIED
ON
ON
UNUSED
ON
ON
EM-8288 Rev.2 P. 2 / 8

Advertisement