4.7 Function Parameter Description
Name
Number
Parameter Set
Pr.0
Mode
Maximum Power
Pr.1
Point Voltage Ratio
Open Circuit
Pr.2
Voltage
Rated Voltage
Pr.3
Pr.4
Rated Current
Pr.5
Rated Power
AC+PV
Pr.6
Power Supply mode
Frequency
Pr.7
Adjustment
Mode
Running Control
Pr.8
Mode
Pr.9
Hour
Pr.10
Minute
Frequency Upper
Pr.11
Limit
Scope
0: Parameter can be read and edited. Other
parameter values cannot be modified until
this parameter is modified to 0.
1: All parameters can only be read.
0-2
2. Restores user parameters (parameters of this
table) to factory values.
The ratio of MPP voltage (Vmp) to open circuit
0.00-1.00
voltage (Voc) of PV array. Unit: 0.01
Open circuit voltage (Voc) of the PV array.
1-1000
Unit: VDC
Associated with the startup PV voltage
Rated voltage of the motor load
1-1000
Associated with the output V/F curve
Rated AC output current. Associated with
0.1-300.00
protection thresholds such as overload and over
current
Rated power of the pump motor. Unit:kW
0.1-300.00
Associated with the power value for PV/AC power
supply switching
0: AC+PV hybrid mode, motor keeps running at
rated frequency when there is AC power input.
0-1
1: Solar priority power supply mode.
0: Panel setting, the frequency is determined by
Pr.12.
1: MPPT way, automatically adjust the frequency
0-5
according to the light condition.
2-5: Reserved
0: Panel control mode.
1: Full automatic operation.
2: Terminal control mode.
3-6: Reserved.
0-6
Note: Under different running modes,
the panel stop button is always valid.
Once
it is pressed the panel is shut
down. To enable press Run button.
Hour required to be corrected.
0-23
Minute required to be corrected.
0-59
The upper limit of output frequency of current
0-Pr.13
operation.
23
Description
Factory
Set
Value
1
0.85
180V
500V
220V
380V
According
to inverter
rating
According
to inverter
rating
1
1
1
0
0
50.00Hz