Malfunction Of System - Daikin Perfera RXM R Series Service Manual

Split r32
Table of Contents

Advertisement

2
|
Troubleshooting
2.5.33 UH-00 – Malfunction of system
Service manual
32
Trigger
In case of connection with
multi indoor units, when
error UA, U0 or A5 occurs
in other indoor unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check all other indoor units for the following error codes. If found, see
"2.5 Error based
troubleshooting" [
▪ A5-00 – Outdoor unit: High pressure peak cut / freeze protection problem
▪ U0-00 – Outdoor unit: Shortage of refrigerant
▪ UA-00 – Indoor unit, outdoor unit mismatching problem
Possible cause: Error on other indoor unit.
2 Perform a check of the indoor unit main PCB. See
4
PCB" [
 102].
Possible cause: Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Effect
Unit will stop operating.
4
 9] to solve the specific error.
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
Reset
Auto reset.
"3.9  Indoor unit main
FVXM25~50A
Split New Perfera R32