To perform an electrical check of the compressor
Service manual
50
1 Turn OFF the respective circuit breaker.
2 Visually check:
▪ For oil drops around the compressor. Locate and fix as needed.
▪ Pipes for signs of damage. Replace pipes as needed.
3 Check that the compressor bolts are correctly fixed. Fix as needed.
4 Check that the compressor wire terminals cover is correctly installed and
fixed. Correct as needed.
5 Check the compressor dampers for any damage.
a
1 Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Yes
No
1 First perform a mechanical check of the compressor, see
4
procedures" [
 49].
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Remove the cover of the compressor wire terminals.
a
Action
Perform an electrical check of the
compressor, see
"Checking
4
procedures" [
 49].
Replace the compressor, see
4
procedures" [
 55].
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
"Repair
"Checking
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01