Figure 3: PW-7000 Port Wiring
Cabinet Tamper and Power Failure Input Wiring
Figure 4: PW-7000 TMP and FLT Terminals
Inputs TMP and FLT are used for monitoring cabinet tamper and power failure with
normally closed contacts. These two inputs are for contact closure monitoring
only; do not use end-of-line (EOL) resistor(s). If these inputs are not used, install a
short piece of wire at the input to indicate a safe condition.
24
PW-7000 (PW7K1IC) Installation and Configuration Guide, Document 800-25673V1