S1
S2
S3
ON
ON
OFF
OFF
OFF
OFF
The PW-7000 DIP switches need to be set twice:
1. Configure the S4-S3-S2-S1 DIP switches to off-off-on-off to set the default
2. Apply power to the panel to set the IP address.
3. Change the S4-S3-S2-S1 combination to off-off-off-on. (DIP switch 1 is "read
4. Create users. See
5. Set the S4-S3-S2-S1 combination to off-off-off-off.
6. Configure the host port(s) for IP Server and/or IP Client communications. See
Factory Default Communication Parameters: Interface 1 (Port 0)
Network: static IP address
Subnet Mask: Default Gateway
Default Gateway
DNS Server
Primary Host port: IP server,
Data Security: TLS if Available,
port 3001, communication
address
Alternate Host Port
18
PW-7000 (PW7K1IC) Installation and Configuration Guide, Document 800-25673V1
S4
Selection
OFF
Unless the network administrator reserves an IP address for the panel (based on the
controller board's Media Access Control (MAC) address), the PW-7000 uses
Dynamic Host Configuration Protocol (DHCP) to obtain an IP address from the
network DHCP server.
When power is applied with the switches in this position, there is a ten second
window (when LEDs 1and 2 flash alternately with LEDs 3 and 4), during which
memory is cleared if switch 1 or switch 2 is changed to OFF. When switch 1 or 2 is
changed to OFF, only LED 2 flashes and memory begins to be cleared. This period of
clearing lasts several minutes. When the memory has been cleared, the LED pattern
changes to the flashing of LEDs 1 and 4. The panel then reboots by itself. All data in
memory is erased except the serial number, MAC address, hardware revision, and
OEM code.
ON
DIP4 = ON -> Legacy Mode, PW7K1IC works as PW6K1IC.
DIP4 = OFF -> Native Mode, PW7K1IC Supported Functions and Capabilities,
Readers and IN/OUTPUTs on PW7K1IC can be used.
TCP/IP address to 192.168.0.251.
on the fly"). This sets the login to the default user ID ("admin") and password
("password") for Ethernet communications.
User Configuration
Host Communication
hardware networking when you log in again.
for instructions.
for instructions. This will enable both TCP/IP and serial
192.168.0.251
255.255.0.0
192.168.0.1
192.168.0.1
0
Disable