Profinet Coupler Unit Specifications - Omron PROFINET NX-PNC202 User Manual

Machine automation controller coupler unit
Table of Contents

Advertisement

3 Specifications and Application Procedures
3-1-3

PROFINET Coupler Unit Specifications

Model
Number of connectable NX Units
NX-Bus refreshing method
NX bus I/O data size
Ethernet connection
Unit power
supply
I/O power
supply
NX Unit power consumption
Current consumption from I/O power
supply
Dielectric strength
Insulation resistance
USB port
Dimensions (width height depth)
Weight
3 - 4
Item
Power supply voltage
NX Unit power supply
capacity
NX Unit power supply
efficiency
Isolation method
Current capacity of
power supply terminals
Power supply voltage
Maximum I/O power sup-
ply current
Current capacity of
power supply terminals
Specification
NX-PNC202
63 Units max
Free-Run refreshing
Input: up to 512 bytes
Output: up to 512 bytes
RJ45(2 port) with switching hub(Layer 2), 100Mbps, full-duplex,
*1
auto-negotiate
Max length of Ethernet cable: 100m
24 VDC (20.4 to 28.8 VDC)
10 W max.
Refer to Installation orientation and restrictions for details.
70%
No isolation between NX Unit power supply and Unit power sup-
ply terminals
4 A max.
5 to 24 VDC (4.5 to 28.8 VDC)
10 A
Refer to Installation orientation and restrictions for details.
10 A max.
1.60 W max.
10 mA max. (for 24 VDC)
510 VAC for 1 min,
leakage current: 5 mA max. (between isolated circuits)
Ω min.
100 VDC, 20 M
(between isolated circuits)
USB 2.0(Full speed: 12Mbbs), Type-B, Max. 5m
46 mm * 100 mm * 71 mm
150 g max
NX-series PROFINET Coupler Unit User's Manual (W623)