3.3 - Default Settings
The ReadyLink™ Ethernet/IP™ LDT out of the box default settings will
be DHCP Enabled and the switches will be set to 255.
(Initialized to "out of box" condition)
IP Address:
Subnet Mask:
Gateway Address:
DHCP
The default baud rate and duplex mode are Auto/Auto. Auto/Auto,
supports autonegotiation on both the baud rate (100/10) and the duplex
mode (full/half).
3.4 - Using IPconfig Utility Program
An IPconfig utility as well as the EDS files are available on our website
www.ametekfactoryautomation.com.
Feedback category under the ReadyLink Network LDT product. Select
Literature to access these downloads. The IPconfig utility program
allows the user to detect any AMETEK Network LDT on the network,
even if the unit's configuration is outside the host's subnet.
Step 1: Connect Network LDT to your network.
Cable connections must be made to the Network LDT for both
communications and power and the switches in the Rapid Recall™
module must be set to 255.
Step 2: Access Network LDT
1. Make sure the configuration DIP switches are set to 255.
2. Turn Power on to the LDT.
3. Open the utility program and press scan. The IP configuration for
the AMETEK Network LDT will be displayed. The device can be
identified by the MAC ID which is found on the product's label.
Phone: 248-435-0700 Toll Free: 800-635-0289 Fax: 248-435-8120 www.ametekfactoryautomation.com
192.168.1.1
255.255.255.0
192.168.1.254
Enabled (on)
They are located in the Linear
Step 3: Program new IP address
1. Double click on the IP address you wish to change.
2. Enter the desired IP address, subnet mask and gateway. Verify that
the DHCP button is set to Off.
3. Select "Set".
4. The new IP address will be assigned and the screen will default
back to the home page. To see the new IP address press "Scan".
®