Chapter 8 LED Summary

The RapidRecall Configuration Module is equipped with 4 Network Status LED's and a tri-color LED labeled LDT, to help while troubleshooting. The
chart below explains the possible LED colors and the faults they represent.
These LEDs are labeled Link1, Net, Mod, Link 2 and LDT. The top row of LEDs will be used to display diagnostics and network status. The bottom
row LDT LED will be used to display the health of the Linear Transducer.
Network LED Functionality
Network LED
Indicator
Status
Number
LINK 1
Green
The module senses a link on connection 1.
Flashing
The LINK 1 LED flashes each time a packet is
received or transmitted.
Green Off
The module does not sense a link.
LINK 2
Green
The module senses a link on connection 2.
Flashing
The LINK 1 LED flashes each time a packet is
received or transmitted.
Green Off
The module does not sense a link.
NET-
Off
The module has no power or no IP address is
Network
assigned.
Status
Green On
The module has at least one established Ethernet
IP connection.
Green
There are no Ethernet/IP connections established
Flashing
to the module.
Red Flashing
One or more of the connections in which this
module is the target has timed out. This state
is only left if all times out connections are re-
established or if the module is reset.
Red On
The module has detected that its IP address is
already in use.
Green/Red
The module is performing a power on self-test.
Flashing
MOD-
Off
No power is applied to the module.
Module
Green
The module is operating correctly.
Status
Flashing
Indicator
Red Flashing
A minor recoverable fault has been detected.
Red On
A major internal error has been detected.
Green/Red
The module is performing a power on self-test.
Flashing
Phone: 248-435-0700 Toll Free: 800-635-0289 Fax: 248-435-8120 www.ametekfactoryautomation.com
LDT LED Status Indicator
LED Status
Summary
Description
Steady Off
No power
No power to LDT or internal power supply has
failed. Verify that incoming M12-A power cable
is connected and supplying a voltage between
7 to 30vdc.
Solid Green
Power is
LDT is working and detecting a good magnet
applied and
signal. Note: Network communications are not
magnet
necessary to get a solid Green LDT.
signal is
detected
Solid Red
No magnet
Magnet is not detected. Verify that magnet was
signal de-
on guide tube when power was applied. Remove
tected
power, verify magnet is on the guide tube, re-
apply power.
Flashing Red
Major fault
Consult factory or network troubleshooting guide.
Slow Flashing
Max ACG
AGC gain has been set to its maximum value,
Red/Green -
Gain Set
verify that magnet was on the guide tube when
1 Sec Red/
power was applied. Remove power, verify
.25 Sec
magnet is on the guide tube, re-apply power.
Green
Flashing
Minor fault
Consult factory or network troubleshooting guide.
Green
NOTE: If there is ever a loss of magnet, the LDT LED will turn red and
the unit will transmit a fault message to the Network that the unit has
lost its signal.
®