SIMATIC
ET 200eco PN
Communication module CM 8x
IO-Link + DI 4x24VDC M12-L
(6ES7148-6JG00-0BB0
Equipment Manual
10/2024
A5E49284833-AD
Introduction
Industrial cybersecurity
Product overview
Wiring
PROFINET IO
EtherNet/IP
Modbus TCP
Technical specifications
Dimension drawing
Parameter data record
1
2
3
4
5
6
7
8
A
B

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SIMATIC ET 200eco PN and is the answer not in the manual?

Questions and answers

Summary of Contents for Siemens SIMATIC ET 200eco PN

  • Page 1 Introduction Industrial cybersecurity SIMATIC Product overview ET 200eco PN Communication module CM 8x Wiring IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 PROFINET IO Equipment Manual EtherNet/IP Modbus TCP Technical specifications Dimension drawing Parameter data record 10/2024 A5E49284833-AD...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Introduction............................Introduction ET 200eco PN Master..................Industry Mall........................Siemens Industry Online Support..................Guide to ET 200eco PN M12-L................... 1.4.1 Information classes ET 200eco PN M12-L................1.4.2 Basic tools........................1.4.3 S7 Port Configuration Tool (S7-PCT).................. 1.4.4 MultiFieldbus Configuration Tool (MFCT)................
  • Page 4 Table of contents EtherNet/IP............................42 Functions/parameters/address space................. 42 6.1.1 Supported EtherNet/IP functions..................6.1.2 Parameters........................43 6.1.3 Explanation of the parameters..................44 6.1.4 Update time of the I/O data....................46 6.1.5 Example address space..................... 47 Diagnostics........................49 6.2.1 Status and error displays for EtherNet/IP................49 Modbus TCP............................
  • Page 5: Introduction

    • On the part of the documentation to which particular attention should be paid. Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP).
  • Page 6: Siemens Industry Online Support

    For answers and solutions concerning automation technology. • mySupport Your personal working area in Industry Online Support for messages, support queries, and configurable documents. This information is provided by the Siemens Industry Online Support in the Internet (http://www.siemens.com/automation/service&support). Guide to ET 200eco PN M12-L 1.4.1 Information classes ET 200eco PN M12-L The documentation for the SIMATIC ET 200eco PN M12-L distributed I/O system is arranged...
  • Page 7: Device Information

    With the TIA Selection Tool , you can generate a complete order list from your product selection or product configuration. You can find the TIA Selection Tool on the Internet. (https://support.industry.siemens.com/cs/ww/en/view/109767888) Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 Equipment Manual, 10/2024, A5E49284833-AD...
  • Page 8 You can find SIEMENS PRONETA Basic on the Internet: (https://support.industry.siemens.com/cs/ww/en/view/67460624) SIEMENS PRONETA Professional is a licensed product that offers you additional functions. It offers you simple asset management in PROFINET networks and supports operators of automation systems in automatic data collection/acquisition of the components used through various functions: •...
  • Page 9: S7 Port Configuration Tool (S7-Pct)

    1.4 Guide to ET 200eco PN M12-L SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
  • Page 10: Multifieldbus Configuration Tool (Mfct)

    MultiFieldbus- and DALI-devices. In addition, the MFCT offers convenient options for mass firmware updates of ET 200 devices with MultiFieldbus- support and reading service data for many other Siemens devices. Functional scope of the MFCT • MultiFieldbus configuration:...
  • Page 11: Simatic Technical Documentation

    Online Support: Industry Online Support International https://support.industry.siemens.com/cs/ww/en/view/109742705 Watch this short video to find out where you can find the overview directly in Siemens Industry Online Support and how to use Siemens Industry Online Support on your mobile device: Quick introduction to the technical documentation of automation products per video ( https://support.industry.siemens.com/cs/us/en/view/109780491...
  • Page 12: Application Examples

    Manuals, characteristics, operating manuals, certificates • Product master data You can find "mySupport" on the Internet. (https://support.industry.siemens.com/My/ww/en) Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products.
  • Page 13: Industrial Cybersecurity

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to...
  • Page 14: Cybersecurity-Relevant Information

    Corrective measures for known risks Corrective measures for known risks are announced on the Siemens ProductCERT and Siemens CERT (https://siemens.com/productcert) web page. You can find more information on SIEMENS ProductCERT in the System Manual (https://support.industry.siemens. com/cs/ww/en/view/109778292). Secure decommissioning You can find information on secure decommissioning in the...
  • Page 15: Product Overview

    Product overview Properties Article number 6ES7148-6JG00-0BB0 View of the module Figure 3-1  View of the CM 8xIO-Link + DI 4x24VDC M12-L communication module Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 Equipment Manual, 10/2024, A5E49284833-AD...
  • Page 16 Product overview 3.1 Properties Properties The module has the following technical properties: • IO-Link master according to IO-Link specification V1.1 • Using the MultiFieldbus function, it connects the ET 200eco PN M12‑L distributed I/O system with one of the following bus protocols: – PROFINET IO –...
  • Page 17: Other Components

    • M12 sealing cap See also You can find additional information on the accessories in the ET 200eco PN M12-L distributed I/O system (http://support.automation.siemens.com/WW/view/en/109774008) system manual. Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 Equipment Manual, 10/2024, A5E49284833-AD...
  • Page 18: Operator Controls And Display Elements

    Product overview 3.2 Operator controls and display elements Operator controls and display elements The following figure shows the operator controls and display elements of the CM 8xIO-Link + DI 4x24VDC M12-L communication module. ① PN/MF (LAN): Sockets for connecting MultiFieldbus ② RN/NS: RUN/network status LED ③...
  • Page 19: Functions

    Product overview 3.3 Functions Functions IO-Link is a point-to-point connection between an IO-Link master and an IO-Link device. On the IO-Link master, you can use IO-Link devices as well as conventional sensors/actuators with unshielded standard cables using proven 3-wire technology. IO-Link is downward-compatible to conventional digital sensors and actuators.
  • Page 20: Reset Communication Module To Factory Settings

    • MFCT Factory Reset PROFINET factory reset You can find additional information on the PROFINET factory reset in the ET 200eco PN M12-L distributed I/O system (http://support.automation.siemens.com/WW/view/en/109774008) system manual. Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 Equipment Manual, 10/2024, A5E49284833-AD...
  • Page 21 • Non-volatile memory is reset (content of the IO-Link data memory is lost) MFCT Factory Reset You can find additional information on the PROFINET factory reset in the ET 200eco PN M12-L distributed I/O system (http://support.automation.siemens.com/WW/view/en/109774008) system manual. Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0...
  • Page 22: Wiring

    Wiring Terminal and block diagram The following figure shows an example of the pin assignment for Port Class A and Port Class ① Bus interface with integrated 2-port switch Supply voltage 1L+ (non-switched) ② Monitoring Ground 1M (non-switched) ③ IO-Link/DI circuit (1L+, 1M) Load voltage 2L+ (switched) ④...
  • Page 23: Pin Assignment

    Wiring 4.2 Pin assignment X14 to X17 IO-Link Port Class B MT/IO MAINT/IO status LED Infeed of supply voltages X1 P1R MultiFieldbus interface X1 Port 1 Loop-through of supply voltages X2 P2R MultiFieldbus interface X1 Port 2 Input signal Ground with reverse polarity protection, derived from 1M (non-switched) Figure 4-1  Terminal and block diagram Pin assignment...
  • Page 24 Wiring 4.2 Pin assignment Pin assignment of the IO-Link sockets The table below shows the pin assignments of the 8 sockets for the connection of IO-Link. Table 4-2  Pin assignment of the IO-Link sockets Assignment Front view of the sockets Port Class A Port Class B 24V encoder supply 1Us Input signal DI...
  • Page 25 (Port Class A compatibility) to connect devices with Port Class A to the communications module CM 4xIO-Link 4xM12. For more information on the IO-Link system, please see the IO-Link system (http://support.automation.siemens.com/WW/view/en/65949252) function manual. NOTE Reverse polarity protection To ensure reverse polarity protection, use the ground 1M supplied by the I/O device on pin 3 of the corresponding socket.
  • Page 26 Wiring 4.2 Pin assignment Pin assignment of the socket for loop-through of the supply voltage (M12 L-coded) The table below shows the pin assignment of the M12 L-coded socket for loop-through of the supply voltage. Table 4-4  Pin assignment of the supply voltage socket Assignment of the core color Assignment Front view of the socket...
  • Page 27: Profinet Io

    PROFINET IO Parameters/address space 5.1.1 Parameters Parameters The following table shows the parameters that you can set for each port (each submodule) of the IO-Link master CM 8xIO-Link + DI 4x24VDC M12-L. Table 5-1  Diagnostics and port parameters Parameters Value range Default Scope with configura­...
  • Page 28: Explanation Of The Parameters

    PROFINET IO 5.1 Parameters/address space Parameters Value range Default Scope with configura­ tion software, e.g. STEP 7 (TIA Portal) • Type compatible (V1.1) with Backup&Restore • Type-compatible (V1.1) with Restore Port cycle time* As short as possible Channel * Only effective if you use the "IO-Link manual" port mode. 5.1.2 Explanation of the parameters Diagnostics: Undervoltage 1L+...
  • Page 29: Input Delay

    PROFINET IO 5.1 Parameters/address space Diagnostics: Wire break detection and alarm Activates wire break detection and enabling of diagnostics for the digital input. In the event of an interruption of the cable between the encoder and I/O device, a diagnostics alarm is generated.
  • Page 30: Operating Mode

    PROFINET IO 5.1 Parameters/address space Port configuration without S7-PCT This parameter releases the port configuration without S7-PCT for the module. NOTE Changes to the port configuration If you have assigned the IO-Link device parameters via port configuration without S7-PCT, or have configured the port as a digital input, digital output or deactivated, you can no longer change the port configuration via S7-PCT.
  • Page 31: Address Space

    • ET 200AL DIQ 4+DQ 4x 24 V DC/0.5 A (6ES7143-5BF00-0BL0), only on the sockets X14 - X17 See also You can find out more about the vendor ID and the device ID of an IO-Link device on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109748852). 5.1.3 Address space Introduction The IO-Link master CM 8xIO-Link + DI 4x24VDC M12-L has eight ports.
  • Page 32 PROFINET IO 5.1 Parameters/address space • ET 200AL DIQ 4+DQ 4x 24 V DC/0.5 A • IO-Link 1 I/1 O + PQI • IO-Link 2 I + PQI • IO-Link 2 I/2 O + PQI • IO-Link 4 I/4 O + PQI •...
  • Page 33 I/O device with digital inputs without value status. The addresses of the channels are derived from the start address. Figure 5-2  Address space DI 4x24VDC Reference For more information, please refer to the IO-Link system (http://support.automation.siemens.com/WW/view/en/65949252) function manual. Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 Equipment Manual, 10/2024, A5E49284833-AD...
  • Page 34: Interrupts/Diagnostics Alarms

    PROFINET IO 5.2 Interrupts/diagnostics alarms Interrupts/diagnostics alarms 5.2.1 Status and error displays LED displays The following figure shows the LED display of the CM 8xIO-Link + DI 4x24VDC M12-L communication module. ① RN/NS: RUN/network status LED ② ER/MS: ERROR/module status LED ③...
  • Page 35 PROFINET IO 5.2 Interrupts/diagnostics alarms Behavior of the LEDs RN/NS (RUN/network status), ER/MS (ERROR/module status) and MT/IO (MAINT/IO status) Table 5-2  Error display of the LED Meaning Remedy RN/NS ERR/MS MT/IO (yel­ (green) (red) low) No or insufficient supply Check the supply voltage. voltage Test of LEDs during startup: The three LEDs light up simul­...
  • Page 36 PROFINET IO 5.2 Interrupts/diagnostics alarms PWR LED Table 5-3  Status display of the PWR LED PWR LED Meaning Load voltage 2L+ is missing or too low Load voltage 2L+ present LEDs P1 LK and P2 LK The following table describes the behavior of LEDs that indicate the connection status with a PROFINET IO controller or a PROFINET switch.
  • Page 37: Interrupts

    PROFINET IO 5.2 Interrupts/diagnostics alarms Channel status/channel error LEDs IO-Link The LEDs of IO-Link port class A and port class B have the same behavior. LEDs Meaning Channel status/error Input or output value is 0 or port is disabled. IO-Link communication established, active device or channel fault. At startup or permanently, if no functional IO-Link device was found.
  • Page 38: Hardware Interrupts

    PROFINET IO 5.2 Interrupts/diagnostics alarms Hardware interrupts All IO-Link events of the type Notification generated by the IO-Link device are mapped to the hardware interrupts of the assigned submodule. The coding of the additional alarm information to the PROFINET standard "ProcessAlarmReason"...
  • Page 39 PROFINET IO 5.2 Interrupts/diagnostics alarms In the "IO-Link Device Diagnostics - Page 2" (CET 0x9501 ) the IO-Link event codes in the range 0x8000 - 0xFFFF are displayed directly: ECET = (IO-Link Event Code – 0x8000 Table 5-6  Overview of error types IO-Link device diagnostics IO-Link event Error type Extended error type...
  • Page 40: Maintenance Events

    ISDU batch failed Parameter inconsistency (24578 See also Diagnostics function manual (https://support.industry.siemens.com/cs/ww/en/view/59192926) 5.2.3.2 Maintenance events Maintenance events All IO-Link events of the type Warning generated by the IO-Link device or port are mapped to the PROFINET diagnostics alarm of the "Maintenance" type of the assigned submodule. The aim is the early detection and elimination of potential faults.
  • Page 41: Process Alarm Events

    PROFINET IO 5.2 Interrupts/diagnostics alarms 5.2.3.3 Process alarm events Hardware interrupt events All IO-Link events (event codes) of the Notification type that are generated by the IO-Link device are mapped to the PROFINET process alarm of the assigned submodule. The additional alarm information read out using RALRM contains the relevant IO-Link event code.
  • Page 42: Ethernet/Ip

    EtherNet/IP Functions/parameters/address space 6.1.1 Supported EtherNet/IP functions Supported functions The table below shows the functions that the I/O device supports with EtherNet/IP. Supported functions Remarks I/O communication with scanner FW 5.1.x or higher Parameter assignment FW 5.1.x or higher Reading diagnostics FW 5.1.x or higher Normative CIP objects FW 5.1.x or higher...
  • Page 43: Parameters

    EtherNet/IP 6.1 Functions/parameters/address space Supported CIP objects for EtherNet/IP The table below shows the CIP objects that the I/O device supports with EtherNet/IP. Supported CIP objects Remarks Identity object FW 5.1.x or higher Assembly object FW 5.1.x or higher Connection Manager object FW 5.1.x or higher TCP/IP Interface object FW 5.1.x or higher...
  • Page 44: Explanation Of The Parameters

    EtherNet/IP 6.1 Functions/parameters/address space Parameters Value range Default Effective range with configuration soft­ ware, for example, MFCT DeviceID* Device ID of the con­ Channel nected IO-Link device Inspection Level/Data Storage* • Same type (V1.0) Type-compatible Channel without (V1.1) with Backup&Restore Backup&Restore •...
  • Page 45: Operating Mode

    EtherNet/IP 6.1 Functions/parameters/address space Hardware interrupt (device notification) Enable of the hardware interrupt for the selected IO-Link port. The possible hardware interrupts are dependent on the IO-Link device used. Additional information on the hardware interrupts can be found in the description of the IO-Link device used.
  • Page 46: Update Time Of The I/O Data

    Set the IO-Link cycle time at the corresponding port. See also You can find out more about the vendor ID and the device ID of an IO-Link device on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109748852). 6.1.4 Update time of the I/O data You can estimate the typical update time for an I/O cycle as follows:    ...
  • Page 47: Example Address Space

    EtherNet/IP 6.1 Functions/parameters/address space 6.1.5 Example address space Configuration example The following figure shows the configuration for this example in MFCT: Figure 6-1  MFCT IO-Link master Input range The following table shows the input range for the example configuration: Slot Subslot DataItem Description CM 8x IO-Link + DI 4x24VDC M12-L 8xM12 V5.1 / input data status...
  • Page 48: Output Range

    IO-Link 1 I/ 1 O + PQI Output_data_1_Byte IO-Link 1 I/ 1 O + PQI See also You can find more information in the MultiFieldbus (https://support.industry.siemens.com/cs/ww/en/view/109773209) function manual. Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 Equipment Manual, 10/2024, A5E49284833-AD...
  • Page 49: Diagnostics

    EtherNet/IP 6.2 Diagnostics Diagnostics 6.2.1 Status and error displays for EtherNet/IP LED displays The following figure shows the LED display of the CM 8xIO-Link + DI 4x24VDC M12-L communication module. ① RN/NS: RUN/network status LED ② ER/MS: ERROR/module status LED ③ MT/IO: MAINT/IO status LED ④...
  • Page 50 EtherNet/IP 6.2 Diagnostics Behavior of the LEDs RN/NS (RUN/network status), ER/MS (ERROR/module status) and MT/IO (MAINT/IO status) on EtherNet/IP The LEDs display the status with the highest priority if there are different LED states due to overlaid events. (0 = off, 1 = green flashing, 2 = green, 3 = yellow, 4 = red flashing, 5 = red) The following table shows the meaning of the RN/NS, ER/MS LEDs and MT/IO LEDs for EtherNet/IP: Table 6-2  Error display of the LEDs...
  • Page 51 EtherNet/IP 6.2 Diagnostics LEDs Meaning Remedy Test of LEDs during startup: The three LEDs light up simultaneously for Flashes Flashes Flashes approximately 0.25 s in red. Then for approximately 0.25 s in green. Hardware or firmware defective. • You can read out the service data with MFCT.
  • Page 52 EtherNet/IP 6.2 Diagnostics Channel status LEDs DI Table 6-5  Status displays of the DI0, DI1, DI2, and DI3 LEDs LEDs Meaning Channel status/channel error Process value = 0 Process value = 1 Channel status/channel error LEDs IO-Link The LEDs of IO-Link port class A and port class B have the same behavior. LEDs Meaning Channel status/error...
  • Page 53: Modbus Tcp

    Modbus TCP Functions/parameters/address space 7.1.1 Supported Modbus TCP functions Supported functions The table below shows the functions that the I/O device supports with Modbus TCP. Supported functions RegLayoutVersion Remarks I/O communication with Modbus client V1.0 FW 5.1.x or higher Free user registers (e.g. for coordination of the redundancy) V1.0 FW 5.1.x or higher Device information...
  • Page 54: Parameters

    Modbus TCP 7.1 Functions/parameters/address space 7.1.2 Parameters Parameters The following table shows the parameters that you can set for each port (each submodule) of the IO-Link master CM 8xIO-Link + DI 4x24VDC M12-L. Table 7-1  Diagnostics and port parameters Parameters Value range Default Effective range with configuration soft­...
  • Page 55: Explanation Of The Parameters

    Modbus TCP 7.1 Functions/parameters/address space 7.1.3 Explanation of the parameters Diagnostics: Missing 2L+ Enable of the diagnostics for no or insufficient load voltage. Diagnostics: Undervoltage 1L+ Enabling of the diagnostics for insufficient supply voltage 1L+. Diagnostics port This parameter enables the diagnostics for the selected IO-Link port. In the diagnostics A distinction is made between error and maintenance interrupts.
  • Page 56: Update Time Of The I/O Data

    Set the IO-Link cycle time at the corresponding port. See also You can find out more about the vendor ID and the device ID of an IO-Link device on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109748852). 7.1.4 Update time of the I/O data You can estimate the typical update time for an I/O cycle as follows:    ...
  • Page 57: Example Address Space

    Modbus TCP 7.1 Functions/parameters/address space 7.1.5 Example address space Configuration example The following figure shows the configuration for this example in MFCT: Figure 7-1  MFCT IO-Link master Input range The following table shows the input range for the example configuration: Slot Subslot DataItem Description...
  • Page 58 IO-Link 1 I/ 1 O + PQI Output_data_1_Byte IO-Link 1 I/ 1 O + PQI See also You can find more information in the MultiFieldbus (https://support.industry.siemens.com/cs/ww/en/view/109773209) function manual. Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 Equipment Manual, 10/2024, A5E49284833-AD...
  • Page 59: Diagnostics

    Modbus TCP 7.2 Diagnostics Diagnostics 7.2.1 Status and error displays for Modbus TCP LED displays The following figure shows the LED display of the CM 8xIO-Link + DI 4x24VDC M12-L communication module. ① RN/NS: RUN/network status LED ② ER/MS: ERROR/module status LED ③...
  • Page 60 Modbus TCP 7.2 Diagnostics Behavior of the LEDs RN/NS (RUN/network status), ER/MS (ERROR/module status) and MT/IO (MAINT/IO status) on modbus TCP The LEDs display the status with the highest priority if there are different LED states due to overlaid events. (0 = off, 1 = green flashing, 2 = green, 3 = yellow, 4 = red flashing, 5 = red) The following table shows the meaning of the RN/NS, ER/MS LEDs and MT/IO LEDs for Modbus TCP: Table 7-2  Error display of the LEDs...
  • Page 61 Modbus TCP 7.2 Diagnostics PWR LED Table 7-3  Status display of the PWR LED PWR LED Meaning Load voltage 2L+ is missing or too low Load voltage 2L+ present P1 LK and P2 LK LEDs Table 7-4  Error display of the P1 LK and P2 LK LEDs LEDs Meaning Remedy...
  • Page 62 Modbus TCP 7.2 Diagnostics Channel status/channel error LEDs IO-Link The LEDs of IO-Link port class A and port class B have the same behavior. LEDs Meaning Channel status/error Input or output value is 0 or port is disabled. IO-Link communication established, active device or channel fault. At startup or permanently, if no functional IO-Link device was found.
  • Page 63: Technical Specifications

    Technical specifications of the CM 8xIO-Link + DI 4x24VDC M12-L communication module The following table shows the technical specifications as of the issue date. You can find a data sheet including daily updated technical specifications on the Internet (https://support.industry.siemens.com/cs/de/en/pv/6ES7148-6JG00-0BB0/td?dl=de). Article number 6ES7148-6JG00-0BB0 General information  ...
  • Page 64 Technical specifications Article number 6ES7148-6JG00-0BB0 Load voltage 1L+   • Rated value (DC) 24 V permissible range, lower limit (DC) 20.4 V • • permissible range, upper limit (DC) 28.8 V • Reverse polarity protection Yes; Against destruction; encoder power supply outputs applied with reversed polarity Load voltage 2L+  ...
  • Page 65 Technical specifications Article number 6ES7148-6JG00-0BB0 Input voltage   • Rated value (DC) 24 V for signal "0" -3 to +5V • • for signal "1" +11 to +30V Input current   • for signal "1", typ. 2.5 mA Input delay (for rated value of input  ...
  • Page 66 Technical specifications Article number 6ES7148-6JG00-0BB0 Interface types   • M12 port Yes; 2x M12, 4-pin, D-coded Number of ports • • integrated switch Protocols   • PROFINET IO Device • Open IE communication Interface types   M12 port   • Autonegotiation •...
  • Page 67 Technical specifications Article number 6ES7148-6JG00-0BB0 Updating times   – Requested Packet Interval (RPI) 2 ms Redundancy mode   DLR (Device Level Ring) – Address area   – Address space per module, max. 300 byte LargeForwardOpen (Class3) – Modbus TCP   Services   –...
  • Page 68 Cat. 3 SIL acc. to IEC 62061 SIL 2 • • remark on safety-oriented shutdown https://sup­ port.industry.siemens.com/cs/de/en/view/39198­ Use in hazardous areas   • Explosion protection category for gas ATEX, UKEX, IECEx, CCCEx for Zone 2 • Explosion protection category for dust...
  • Page 69 Technical specifications Article number 6ES7148-6JG00-0BB0 product functions / security / header   signed firmware update safely removing data Ambient conditions   Ambient temperature during operation   • min. -40 °C max. 60 °C • Altitude during operation relating to sea level   •...
  • Page 70 Technical specifications Power reduction (derating) to total current of outputs, per module, The following derating curves show the load capacity of the transducer supply outputs in relation to the mounting position and the ambient temperature. ① Total current of outputs 1L+ ②...
  • Page 71: Dimension Drawing

    Dimension drawing The following figure shows the dimension drawing of the CM 8xIO-Link + DI 4x24VDC M12-L communication module in front and side view. Figure A-1  Dimension drawing Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0 Equipment Manual, 10/2024, A5E49284833-AD...
  • Page 72: Parameter Data Record

    Parameter data record Dependencies for the configuration When configuring the I/O device, the parameter settings are independent of each other. Error transferring the data record Error transferring the data record The I/O device checks the values of the transferred data record. Only if the values were transferred without errors does the I/O device apply the values from the data record.