Mounting
3.3 Mounting with mounting rail
Installing the mounting rail
The mounting rail with 500 mm length must be cut to length according to your
requirements.
To install the mounting rail with 500 mm length, follow these steps:
1. Drill the mounting holes for screws with 8 mm diameter.
We recommend that, after an initial distance of 12 mm, the mounting holes be provided at
regular intervals of 182 mm.
2. Fasten the mounting rail with the screws.
Figure 3-3
Installing the I/O device
The I/O devices have an attachment point at top and bottom for front mounting and side
mounting.
The mounting rail has a groove at the top and bottom in which the profile screws are simply
screwed in without drilling.
To install the I/O device, follow these steps:
1. Insert a profile screw through the mounting point of the I/O device and in a groove of the
mounting rail.
2. Use the screwdriver to screw the I/O device to the mounting rail.
3. Align the I/O device on the mounting rail.
4. Insert a profile screw through the other mounting point of the I/O device and in the other
groove of the mounting rail.
5. Screw the I/O device to the mounting rail. The tightening torque is 1.5 Nm.
Accessories
The accessories for mounting the distributed I/O device can be found in section
Accessories/spare parts (Page 81).
22
Installing the mounting rail
Distributed I/O system ET 200eco PN M12-L
System Manual, 06/2021, A5E48753295-AC