Siemens SIMATIC ET 200eco PN M12-L System Manual page 39

Hide thumbs Also See for SIMATIC ET 200eco PN M12-L:
Table of Contents

Advertisement

Connecting
4.5 Connecting cables for ET 200eco PN M12-L
Derating of the input currents
The table below shows the maximum permissible input current of the distributed I/O systems
depending on the ambient temperature.
Table 4- 2
Ambient temperature
40 °C
50 °C
60 °C
Note
Adherence to the minimum clearance
The I/O devices may be used at an installation distance of 2 cm up to max. 60 °C ambient
temperature.
If the installation distance to other devices or objects is less than 2 cm, the ambient
temperature must be reduced by 5 K (for example, 60 °C ⇒ 55 °C). This must also be taken
into consideration for the derating diagrams of the device manuals.
38
Deratings of the input currents while maintaining the minimum clearance
Max. input current 1L+
12 A
10 A
8 A
Max. input current 2L+
12 A
10 A
8 A
Distributed I/O system ET 200eco PN M12-L
System Manual, 06/2021, A5E48753295-AC