Main Functions
1.7
Thermostat Control
Outline
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Details
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The temperature difference remains in zone B for the determined monitoring time.
Cooling
Heating
Refer to Temperature Control on page 15 for details.
21
(Cooling: 10 minutes, Heating: 10 seconds)
Zone C
–1.0˚C (–1.8˚F)
Zone B
–2.0˚C (–3.6˚F)
Zone A
Zone A
Zone A
Zone B
Zone B
1.5˚C (2.7˚F)
Zone C
Zone C
Room thermistor temperature – target temperature
ON
–0.5˚C (–0.9˚F)
–1.5˚C (–2.7˚F)
OFF
Room thermistor temperature – target temperature
OFF
OFF
2.0˚C (3.6˚F)
0.5˚C (0.9˚F)
ON
ON
SiUS041638EA
(R24628)
(R24629)
Functions and Control