Rotation Pulse Check on the Outdoor Unit PCB

Check No.16
Make sure that the voltage of 320 + 100 V ~ 320 - 50 V is applied.
1. Set operation off and power off. Disconnect the connector S70 or S71.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 4 - 3 is 15 VDC.
4. Check that the rotation command voltage between the pins 4 - 2 is 0 ~ 6.5 VDC.
5. Keep operation off and power off. Connect the connector S70 or S71.
6. Check whether 4 rotation pulses (0 ~ 15 VDC) are input at the pins 4 - 1 when the fan motor is
When the fuse is melted, check the outdoor fan motor for proper function.
Service Diagnosis
rotated 1 turn by hand.
If NG in step 2  Defective PCB
If NG in step 4  Defective Hall IC  Replace the outdoor fan motor.
If OK in both steps 2 and 4
PCB
S70
1
2
3
4
5
6
7
 Replace the outdoor unit PCB (main PCB).
 Replace the outdoor unit PCB (main PCB).
Actual rotation pulse input (0 ~ 15 VDC)
Rotation command voltage (0 ~ 6.5 VDC)
Control voltage 15 VDC
320 VDC
Check
(R19655)
100