Freeze-Up Protection Control; Heating Peak-Cut Control - Daikin FTX-N Series Service Manual

Inverter pair; wall mounted type
Hide thumbs Also See for FTX-N Series:
Table of Contents

Advertisement

SiUS041638EA
3.6

Freeze-up Protection Control

During cooling operation, the signal sent from the indoor unit determines the frequency upper limit
and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is divided into
zones.)
The operating frequency limitation is judged with the indoor heat exchanger temperature.
3.7

Heating Peak-cut Control

During heating operation, the indoor heat exchanger temperature determines the frequency upper
limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
A
B
C
D
E
Functions and Control
13˚C (55.4˚F)
Reset zone
7˚C (44.6˚F)
Up zone
5˚C (41.0˚F)
Keep zone
3˚C (37.4˚F)
Dropping zone
0˚C (32.0˚F)
Stop zone
B
C
D
Indoor heat exchanger
temperature
RX30/36NMVJU(A)
(°C)
60
140.0
57
134.6
54
129.2
52
125.6
47
116.6
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
Indoor heat exchanger
temperature (R2T)
(°F)
Control Specification
(R24574)
Stop zone
A
Dropping zone
Keep zone
Up zone
E
Reset zone
(R23928)
Control