3.0

OPERATING PROCEDURES

The CVT-765 should always be grounded with the provided ground cable before connecting H
and X cables. The transformer bushings should also be grounded before connecting test leads
to the transformer. This will prevent inducing any voltages into the CVT-765. All transformer
bus connections must be removed, and the transformer must be isolated before performing
any tests.
3.1

Connection Diagram

Figure 2. Typical CVT-765 Cable Connections

CVT-765 USER'S MANUAL
REV 1
7