Communication - Macurco DVP-1200 Manual

Detection and ventilation control panel with bacnet
Table of Contents

Advertisement

Macurco
TM
DVP-1200 Manual
NOTE: START TIME and END TIME are entered in 12-hour time format, only entries with START TIME earlier than END TIME are
valid. E.g. 11:00 AM (Start Time) to 01:00PM (End Time) is a valid entry but 11:00PM (Start Time) to 01:00 AM (End Time) is an
invalid entry.
ACTIVE – Timed Mode Control will work only when this field is set to ON. The default setting is OFF. The user can disable the
TIMED MODE for the chosen zone by setting ACTIVE: OFF.
SAVE – Select SAVE and press ENTER to save any changes.

4.6.4 COMMUNICATION?

Menu path: Main Menu-->COMMUNICATION?-- >
4.6.4.1
SERIAL PORT SETTING
Menu path: Main Menu-->COMMUNICATION? -->SERIAL PORT SETTING-->
REV – 1.3.1
Figure 4-47 –
Figure 4-48 –
[34-8708-4770-7 ]
46 |
P a g e