4.2.3.5
Enter key
The enter key is used to select menu items and to confirm any user input.
4.2.3.6
DEL Key
The DEL key is used to delete characters if an incorrect character is entered or is used to delete the event log.
4.2.3.7
Brightness Key
The brightness key is used to turn the LCD display backlight on or off. It is located on the lower left corner of the keypad.

4.3 Normal Status Display

The normal display shows the date and the time, the status and basic configuration of each zone, and the sensor type and
number of sensors connected for each sensor type.
In the middle box, each zone is indicated by "Z" followed by zone number.
All sensors assigned to the zone are listed by their sensor type. They are indicated by the two-letter abbreviation for the gas
type of the sensor.
If a horn/strobe is assigned to the group, it will be indicated by H/Sx where "x" is the horn/strobe number. Similarly, if a relay is
assigned to the group, it will be indicated by Rx where "x" is the relay number.
Lastly, the status of each zone is displayed. In normal operating conditions, it will show "NORMAL". If a sensor in the zone is
indicating a gas level that is greater than the alarm or warning levels, the zone status will show "ALARM" or "WARNING" as
appropriate. If any of the sensors assigned to the zone goes into trouble, then the status of the zone in the main screen is
updated with 'TROUBLE'.
NOTE: If a sensor is part of final system installation and needs to be monitored, it must be assigned to a zone.
REV – 1.3.1
State of the Panel
Alarm
Warning
Trouble
Table 4-1 –
Figure 4-2 –
[34-8708-4770-7 ]
Silence Period
5 minutes
15 minutes
8 hours
23 |
P a g e