Range
Process
±10VDC
±20mA DC
Sensor
24V@60mA, 10V @ 60mA
Excitation
Range
Potentiometer
200Ω minimum
Sensor
10V @ 60mA
Excitation
Range
Load Cell
±15mV, ±30mV,
±150mV
Sensor
10V @ 60mA
Excitation
RTD
Fixed display
range /
resolution
Accuracy /
resolution
Pt100 sensor
excitation
Max lead
resistance
Thermocouple
Temperature
Fixed display
range /
resolution
Accuracy /
resolution
Cold junction
compensation
range
Offset
programmable
32
Technical Specifications
Input Impedance
1MΩ
15Ω
Input Impedance
1MΩ
Input Impedance
100MΩ
J
-150.0°C to
1100.0°C / 0.1°C
-150°C to
1100°C / 1°C
-238.0°F to
2012.0°F / 0.1°F
-238°F to
2012°F / 1°F
±(0.4% rdg+0.6°C) / 0.1°C
±(0.4% rdg+1°C) / 1°C
±(0.4% rdg+1°F) / 0.1°F
±(0.4% rdg+2°F) / 1°F
DPM3 User Manual, 1st Edition
Accuracy
±(0.1% rdg + 1 digit)
±(0.1% rdg + 1 digit)
Accuracy
±(0.1% rdg + 1 digit)
Accuracy
±(0.1% rdg + 1 digit)
Pt100 (3-Wire)
-200.0°C to 800.0°C / 0.1°C
-200°C to 800°C / 1°C
-328.0°F to 1472.0°F/ 0.1°F
-328°F to 1472°F / 1°F
±(0.2% rdg+0.6°C) / 0.1°C
±(0.2% rdg+1°C) / 1°C
±(0.2% rdg+1°F) / 0.1°F
±(0.2% rdg+2°F) / 1°F
<1mA DC
40Ω / cable (balanced)
K
-150.0°C to
1200.0°C / 0.1°C
-150°C to
1200°C / 1°C
-238.0°F to
2192.0°F / 0.1°F
-238°F to
2192°F / 1°F
±(0.4% rdg+0.6°C) / 0.1°C
±(0.4% rdg+0.6°C) / 0.1°C
±(0.4% rdg+1°C) / 1°C
±(0.4% rdg+1°C) / 1°C
±(0.4% rdg+1°F) / 0.1°F
±(0.4% rdg+1°F) / 0.1°F
±(0.4% rdg+2°F) / 1°F
±(0.4% rdg+2°F) / 1°F
-10°C to 60°C (14°F to 140°F)
-19.9° / +99.9°
Resolution
1mV
1µA
Resolution
0.005%
Resolution
1µV
T
-200.0°C to
-150.0°C to
400.0°C / 0.1°C
1300.0°C / 0.1°C
-200°C to
400°C / 1°C
1300°C / 1°C
-328.0°F to
-238.0°F to
752.0°F / 0.1°F
2372.0°F / 0.1°F
-328°F to
752°F / 1°F
2372°F / 1°F
±(0.4% rdg+0.6°C) / 0.1°C
±(0.4% rdg+1°C) / 1°C
±(0.4% rdg+1°F) / 0.1°F
±(0.4% rdg+2°F) / 1°F
N
-150°C to
-238°F to