Download Print this page

Burner Start-Up Cycle Diagnostics; Operating Fault Diagnostics - Riello PRESS 140 T/N Installation, Use And Maintenance Instructions

Heavy oil burners

Advertisement

BURNER START-UP CYCLE DIAGNOSTICS

During start-up, indication is according to the followin table:
Sequences
Pre-purging
Ignition phase
Operation, flame ok
Operating with weak flame signal
Electrical supply lower than ~ 170V
Lock-out
Extraneous light
Key:

OPERATING FAULT DIAGNOSTICS

The control box has a self-diagnostic system, which easily allows identifying the operating faults (RED LED signal).
ITo use this function, wait at least ten seconds from the safety lock out, and then press the reset button for a minimum of 3 sec-
onds.
After releasing the button, the RED LED starts flashing as shown in the diagram below.
RED LED on
wait at least 10 s
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will provide the information on the possible faults, according to the table below:
In the event of a burner lockout, more than two conse-
cutive burner reset operations could cause damage to
the installation. On the third lockout, contact the After-
sales Service.
WARNING
SIGNAL
2 flashes
3 flashes
4 flashes
7 flashes
8 flashes
10 flashes
5831
COLOUR CODE TABLE
Off
Yellow
Press button
for > 3 s
The flame does not stabilise at the end of the safety time:
– faulty photocell;
– faulty or soiled oil valves;
– faulty ignition transformer
– poor burner regulation.
– Not used.
– Light in the chamber before firing.
Loss of flame during operations:
– poor burner regulation;
– faulty or soiled oil valves.
– Faulty thermostat for oil permissive signal;
– Heating resistances blown.
– Wiring error or internal fault;
– Presence of electromagnetic disturbance: use the radio disturbance protection kit
Green
Interval
Signal
If further lockouts or burner faults occur, interventions
must only be made by qualified, authorised personnel
(as indicated in this manual, and in compliance with
the laws and regulations currently in force).
DANGER
PROBABLE CAUSE
12
Colour code
Red
3 s
Signal

Advertisement

loading

This manual is also suitable for:

34368853436886