TECHNICAL DATA

Thermal power - Output
Operation
Fuel
Pump

ELECTRICAL DATA

Motor IE1
Electrical supply
Motor
Ignition transformer
Heaters
Absorbed electrical power
Motor IE2
Electrical supply
Motor
Ignition transformer
Heaters
Absorbed electrical power
Fig. 1
1
- Suction line
2
- Return line
3
- Air shutter opening motor
4
- Pump pressure adjustment screw
5
- Manometer plug (G 1/8)
6
- Vacuometer plug (G 1/2)
7
- Reset push-button of the motor overload relay
8
- Electric board
9
- Cable clamps
10
- Control box reset push-button and lock-out lamp
11
- Adjustment thermostat
12
- Regulating bush for combustion head
13
- Wiring terminal board
14
- Ignition transformer
15
- Filter
16
- Valves group
17
- Manometer
5831
320 / 1600 kW - 28 / 140 kg/h (See page 3)
st
nd
1
stage - 2
stage - 3
Oil with max. viscosity 50 mm
with kit: max. viscosity 500 mm
350 kg/h at 25 bar
Three phase: 220 V +10% -10% ~ 60 Hz without neutral
220-380 V +10% -10% ~ 60 Hz with neutral
15.9 A / 220V - 9.2 A / 380V
Primary: 2 A - Secondary: 2 x 6.5 kV - 35 mA
4 kW
18.6 kW
Three phase: 220 V +10% -10% ~ 60 Hz without neutral
220-380 V +10% -10% ~ 60 Hz with neutral
14.6 A / 220V - 8.5 A / 380V
Primary: 2 A - Secondary: 2 x 6.5 kV - 35 mA
4 kW
18.6 kW
18
- Lamp
19
- Commutator
20
- Low limit thermostat
21
- High limit thermostat
22
- Timer
Quantity
1
rd
stage
2
/s (7°E) at 50°C
2
/s (65°E) at 50°C
Accessories
2
Flexible tubes
2
Nipples
4
Screws
1
Gasket for flange
5
Cable clamps