17 Inspection/maintenance

17.2 Replacing the actuator

Risk of electric shock
▶ Risk of injury or death (if operating
voltage is higher than safe extra low
voltage).
▶ Adjustments are made with the actu-
ator cover removed.
▶ Electric shock can cause severe burns
and fatal injury.
Always disconnect the product from
power supply!
Therefore, have all work performed
only by qualified electricians.
17.2.1 Removing the actuator from the ball valve body
1. Disconnect the actuator A from power supply .
2. Unscrew the hexagon screws 3.
3. Do not lose the washers 2.
4. Remove the actuator A from the ball valve body 1.
GEMÜ B54
DANGER
17.2.2 Disassembling the ball valve body
1
1. Use appropriate protective gear as specified in plant oper-
ator's guidelines.
2. Shut off plant or plant component.
3. Secure against recommissioning.
A
4. Depressurize the plant or plant component.
5. Fully unscrew the nuts 1.
6. Pull out the bolts 3.
7. Remove the ball valve 2.
Important:
▶ Clean all parts of contamination (do not damage the
parts during cleaning) following removal. Check parts for
potential damage; replace if necessary (only use genuine
parts from GEMÜ).
1
17.2.3 Replacement of spare parts
If a spare part must be replaced, it is recommended to
2
likewise replace all spare parts included in the wearing
parts kit.
3
38 / 43
3
2
NOTICE
NOTICE