Emerson NetSure 721NPBB User Instructions page 53

-48v dc power system
Hide thumbs Also See for NetSure 721NPBB:
Table of Contents

Advertisement

NetSure
-48V DC Power System
User Instructions, UM582127000 (Issue AD, January 20, 2014)
Replacing a Battery or Load Disconnect Contactor
Danger! All sources of AC and DC power must be
completely disconnected from this power system
Danger
before performing this procedure. Use a voltmeter to
verify no DC voltage is present on the system busbars
before proceeding.
Note:
In the following procedure, before making busbar-to-busbar
connections, apply a thin coating of electrical anti-oxidizing
compound to the mating surfaces of the busbars.
PROCEDURE
Note:
Refer to
Figure
29,
Figure
procedure is performed.
Removing the Contactor
1.
Verify all AC and DC power sources are disconnected
from the power system.
2.
For the 1-row distribution cabinet, the contactor can be
accessed from the top of the distribution cabinet. For the
2, 3, or 4-row distribution cabinet, the contactor can be
accessed from the rear (and top) of the distribution
cabinet.
3.
For the 2, 3, or 4-row distribution cabinet, remove the
distribution cabinet's rear access panel(s).
Spec. No: 582127000
Model No: 721
NPBB
30,
Figure
31, or
Figure 32
as this
4.
Disconnect the wiring to the contactor by unplugging the
quick disconnects.
5.
Note the orientation of the contactor to ensure the
replacement is installed the same way. Unbolt the
contactor (4-places) and remove. Save all hardware.
Installing the Replacement Contactor
1.
Position the replacement contactor oriented the same
way as the old.
2.
Secure the contactor with the hardware removed above.
Refer to
Figure
hardware build-up and recommended torque.
3.
Replace the wiring to the contactor by plugging-in the
quick disconnects. Refer to
31, or
Figure
32.
4.
For the 2, 3, or 4-row distribution cabinet, replace the
distribution cabinet's rear access panel(s).
Restarting the Power System
1.
Reconnect the AC and DC power sources to the power
system.
2.
Start the power system. Refer to the separate Installation
Instructions (IM582127000) for a startup procedure.
3.
Verify no alarms are active.
[45]
29,
Figure
30,
Figure
31, or
Figure 32
Figure
29,
Figure
Code: UM582127000
Issue AD, January 20, 2014
for
30,
Figure

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netsure acu+582127000

Table of Contents