Technical Data - Siemens 3TM Operating Instructions Manual

Vacuum contactor
Hide thumbs Also See for 3TM:
Table of Contents

Advertisement

Description
Electrical data
Rated voltage U
(phase-to-phase)
r
Rated voltage U
(phase-to-earth)
r
Rated frequency f
r
Rated lightning impulse withstand voltage
Rated short-duration power frequency withstand volt-
age U
d
Rated operating current I
ranging from -40 °C to +70 °C)
)
Thermal current I
*
th
Rated inrush current
Rated breaking current
Rated short-circuit breaking current (limit switch capa-
bility)
Rated short-circuit current (effective value) 1 s
Solenoid actuator
Rated supply voltage U
Start-up power loss, maximum (for max. 1 ms per clos-
ing)
Start-up power loss
Holding mode power loss
Closing time
Optional additional adjustable on-time delay
Off-time (without latching mounted)
Optional additional adjustable off-time delay
24 V DC to 60 V DC
110 V DC to 250 V DC / 100 V AC to 240 V AC
Off-time (with electric tripping)
20

Technical data

Up
(at ambient temperatures
e
)
*
Depending on ambient conditions and temperature
)
**
29 kV for UL
Fig. 13
Electrical data
(-15 % to +10 %)
a
Fig. 14
Rated data of solenoid actuator
1-pole
3TM
12
13
14
kV
7.2
12
kV
4.15
6.9
Hz
kV
60
75
kV
20
32
28
A
A
kA
kA
kA
5
4.5
kA
1-pole
3TM
12/13
14/15
V
24 V DC to 32 V DC
V
48 V DC to 60 V DC
V
110 V DC to 125 V DC / 100 V AC to 120 V AC
V
220 V DC to 250 V DC / 230 V AC to 240 V AC
(VA)
(VA)
(VA)
ms
ms
ms
75 ±10
ms
ms
30 / 60 / 90 ± 10
ms
35 ±10
3-pole
15
32
33
34
35
7.2
12
50-60
60
75
)
42
20
32
28**
/42
450
450
4.5
3.6
5
5
8
3-pole
32/33
34/35
1400
700
10 to 20
55 ±15
50 ±10
40 ±10
50 ±10
35 ±10
9229 0106 176 0-
2020-09-18
36
15
75
20
320
320
3.2
2.65
4.5
36