Storage room
Enclosed, dry, well venti-
lated, and as free from
dust as possible, with a
relative air humidity below
95 %.
Enclosed, dry, well venti-
lated and as free from
dust as possible, with a
maximum relative humid-
ity of up to 90 % per
month.
9229 0106 176 0-
2020-09-18

Storage

Note
During transport and storage, the vacuum contactor must be in the following con-
dition:
OPEN switch position
Unlatched condition (only if unlatching is available).
Note
Risk of corrosion damage if stored improperly!
The vacuum contactor can be stored for up to a year in its transport unit if the stor-
age conditions listed below are met.
If the storage conditions are not met, the vacuum contactor cannot be stored any
longer than 6 months in the transport unit.
If storage of longer than one year is planned, unpack the vacuum contactor from
the transport unit. Further storage must ensure that the vacuum contactor cannot
be damaged.
Transport unit
Storage time
Unopened
Max. 6 months
Unopened
max. 1 year
None
Over 1 year
1) In the storage conditions given above, the capacitors must be reformed after
one year. To do so, apply rated supply voltage via terminal A1/A2 of the elec-
tronic controller for at least 20 minutes.
Transport/storage/packaging
Temperature range
-40 °C to +70 °C
-40 °F to 158 °F
-5 °C to +40 °C
23 °F to 104 °F
1)
-25 °C to +70 °C
-13 °F to 158 °F
Number of
units per
stack
max. 3
max. 3