Table 7 - Setpoints And Values - York J Series Manual

25 through 40 tons
Hide thumbs Also See for J Series:
Table of Contents

Advertisement

Parameter Descriptions and Options
TABLE 7 – SETPOINTS AND VALUES
DESCRIPTION TEXT ON OCC
1.
Unit Type
2.
Dirty Filter Switch
3.
ASCD Override
4.
Run Test
5.
Panel Test
6.
# of Compressors
7.
# of Heat Steps
8.
Heating Type
1
9.
Freezestat
10.
Transducer Package
11.
Reset Lead-Lag
12.
Cooling SAT Limit #1
13.
Cooling SAT Limit #2
14.
Heating SAT Limit
15.
Power Exhaust Config
16.
Economizer Installed
17.
Duct Sensor Hi Limit
18.
Sys X Comp Runtimes
19.
Sys X Comp Starts
2
20.
Exhaust (Fan Runtimes)
21.
Unoccupied Heating
22.
Unoccupied Cooling
23.
Occupied Heating
24.
Occupied Cooling
25.
VAV Cool High Temp
26.
VAV Cool Low Temp
27.
VAV Cool Reset Temp
28.
Duct Static Pressure
29.
Building Pressure
30.
Economizer 1st Stage
31.
Economizer 2nd Stage
32.
SAT Econo Load Heat
33.
Outside Air Enthalpy
34.
Cmfrt Vent High SAT
35.
Cmfrt Vent Low SAT
36.
Warm-Up RAT
37.
Hydro Heat 1st Stage
38.
Hydro Heat 2nd Stage
39.
OA Damper Min Pos #1
40.
OA Damper Min Pos #2
41.
Demand Ventilation
42.
(FlexSys) MSAT Setpoint
43.
(FlexSys) Min Dewpt Diff
44.
Language Option
45.
Measurement Units
46.
Space Sensor Enable
47.
Unocc Override Time
48.
Space Setpt Offset
49.
Fan ON With Sensor
50.
RAT Sensor Enable
51.
Space Temp Alrm Diff
52.
Space Temp Alrm Time
53.
Sens Consist Enable
54.
SAT Control For Cool
55.
SAT Control For Heat
56.
Rev Act Heat Valve
62
2
2
DEFAULT
UNITS
VALUE
CV
OFF
OFF
OFF
OFF
ON or OFF
4
4 or 6
0
0-6
2
None, Gas
OFF
0
OFF
°F
45°F
°F
50°F
°F
160°F
0
NO
inwg
5.0
starts
0
hr
0
hr
0
°F
60°
°F
85°
°F
68°
°F
72°
°F
60°
°F
55°
°F
72°
inwg
1.50
inwg
+0.100
°F
55°
°F
50°
°F
150
btu/lb
28
°F
80°
°F
70°
°F
70°
°F
100°
°F
115°
%
15%
%
30%
ppm
1000
°F
62
°F
3
English
Imperial
Imperial, SI Canada, SI
OFF
min
60 min
°F
3°F
ON
OFF
°F
5°F
min
60 min
OFF
ON
°F
OFF
OFF
Continued on next page
FORM 100.50-NOM7 (808)
VALUE
OCC
RANGE
KEY
CV, VAV, MIT-VAV
Configuration
ON or OFF
Configuration
ON or OFF
Configuration
ON or OFF
Configuration
Configuration
Configuration
Configuration
None, Gas, Electric,
Configuration
HW, or Steam
ON or OFF
Configuration
0 – 3
Configuration
ON or OFF
Configuration
40°-50°F
Configuration
40°-65°F
Configuration
100°-195°F
Configuration
0 - 3
Configuration
YES – NO
Configuration
2.5 – 5.0
Configuration
(> expected value)
Service
(> expected value)
Service
(> expected value)
Service
45°-99°
Setpoint
45°-99°
Setpoint
45°-99°
Setpoint
45°-99°
Setpoint
50°-70°
Setpoint
50°-70°
Setpoint
60°-95°
Setpoint
0.00-5.00
Setpoint
-0.200-+0.200
Setpoint
40°-65°
Setpoint
40°-65°
Setpoint
100 – 195
Setpoint
22-40
Setpoint
60°-85°
Setpoint
60°-85°
Setpoint
50°-85°
Setpoint
75°-150°
Setpoint
75°-150°
Setpoint
0-100%
Setpoint
0-100%
Setpoint
750-1500
Setpoint
55 – 70
Setpoint
1 – 5
Setpoint
English, Spanish
Unit Setup
Unit Setup
ON or OFF
Unit Setup
0-240 min
Unit Setup
0°-5°F
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
0°-25°F
Unit Setup
0-120 min
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup