Menu Navigation and Display Descriptions

"OPERATION DATA" NAVIGATION

The Operation Data key (or Menu Item) will move the
display to the first display item of the Operation Data
group. The Operation Data group of display items will
give the user access to the units' current operating pa-
rameters. The Operation Data group of display items
will be view only and will require no password.
Starting with the first display item, the Operation Data
display items will be as follows:
** OPERATION DATA **
Sys 1 Compressors
Comp A = ON
Comp B = OFF
Line 2 Sys X Compressors
Line 3 Comp A = ON (OFF, FAULT, N/A)
Line 4 Comp B = ON (OFF, FAULT, N/A)
** OPERATION DATA **
Sys 1 Compressors
Suc Press = 100 psig
Dis Press = 325 psig
Line 2 Sys X Compressors
Line 3 Suc Press = XXX PSIG (N/A)
Line 4 Dis Press = XXX PSIG (N/A)
** OPERATION DATA **
Compressor Staging
Next ON = 2-B
Next OFF = Waiting
Line 2 Compressor Staging
Line 3 Next ON = X-X (N/A)
Line 4 Next OFF = X-X (N/A)
42
** OPERATION DATA **
OA Temp = 73.4°F
OA RH = 48%
OA Enth =26.8 btu/lb
Line 2 OA Temp= XXX°F (0.0, ???)
Line 3 OA RH = XXX% (0.0, ???)
Line 4 OA Enth= XX.X btu/lb (0.0)
** OPERATION DATA **
RA Temp = 69.6°F
RA RH = 55%
RA Enth =26.0 btu/lb
Line 2 RA Temp= XXX°F (0.0, ???)
Line 3 RA RH = XXX% (0.0, ???)
Line 4 RA Enth= XX.X btu/lb (0.0)
** OPERATION DATA **
Supply Air Temp
Temp = 57.6°F
Setpt = 58.0°F
Line 2 Supply Air Temp
Line 3 Temp = XXX.X°F (0.0, ???)
Line 4 Setpt = XXX.X°F
** OPERATION DATA **
Supply Duct Pressure
Press = 1.48 inwg
Setpt = 1.50 inwg
Line 2 Supply Duct Pressure
Line 3 Press = X.XX inwg (0.0, ???)
Line 4 Setpt = X.XX inwg (0.0, ???)