BI #4, 5, & 6 , Furnace Module #1, 2, & 3 Status
Gas Heat Stages 1, 2 and 3.
BI #7, Thermostat "G" Input
The thermostat "G" or fan output is connected to BI #7.
BI #7 is monitored when the controller determines that
a thermostat is to be used for temperature control. The
Supply Fan is controlled as follows subject to specific
conditions described in the Constant Volume or Variable
Air Volume sections:
• Turn Supply Fan ON – 24VAC input present.
• Turn Supply Fan OFF - 24VAC input not present.
BI #8, Occupied / Unoccupied Input
The Occupied/Unoccupied input is used to determine
when occupied or unoccupied control modes are to be
used. The source of the input may be a time clock, a
thermostat with a clock function or an occupancy sensor.
The occupancy status is indicated as:
• Occupied – Occupied/Unoccupied 24VAC input
present.
• Unoccupied – Occupied/Unoccupied input 24VAC
not present.
BI #9, Shutdown Input
The Shutdown input will be monitored by the control. The
control will interpret the Shutdown input as follows:
• Shut down condition – Shutdown 24VAC input
present.
• Not in shut down condition – Shutdown 24VAC
input not present.
When the Shutdown input is present, the control will
within 1 second:
• Set all binary outputs to low (de-energize).
• Set all analog outputs to zero volts.
This input will have priority over all operation.
JOHNSON CONTROLS
BI #10, Smoke Purge Input
The Smoke Purge input will monitored by the control.
The control will interpret this input as follows:
• Smoke purge required – Smoke Purge 24VAC input
present.
• Smoke purge not required – Smoke Purge 24VAC
input not present.
When the Smoke Purge input has been continuously
present for 5 seconds or more, the control will:
• Read the Smoke Purge parameter value.
• If the Smoke Purge parameter value is zero, no ac-
tion is taken.
• If the Smoke Purge parameter value is not zero.
• All heating or cooling is shutdown and made un-
available.
• The configured Smoke Purge Operation will be
carried out.
BI #11, Supply Fan Status
An air flow switch is used to verify the status of the Sup-
ply Fan. When air flow is detected, the binary 24VAC
input is present.
Supply Fan Fault:
When the control turns the Supply Fan ON, the Sup-
ply Fan Status input will be monitored following a 60
second start up delay. If the Supply Fan Status input is
not present after the delay the unit is shut down and a
Supply Fan Fault is declared.
If the Supply Fan is operating normally and the Supply
Fan Status input is no longer present, the control will
delay for 30 seconds. If after 30 seconds, the input is not
present, the control will shut down the unit and declare
a Supply Fan Fault.