York J Series Manual page 63

25 through 40 tons
Hide thumbs Also See for J Series:
Table of Contents

Advertisement

DESCRIPTION TEXT ON OCC
57.
Cooling Mode Enable
58.
Heating Mode Enable
59.
Heat Lockout OAT
60.
Cool Lockout OAT
61.
Cooling SAT Alarm
62.
Heating SAT Alarm
63.
Duct Pressure Limit
64.
VAV Occupied Heat
65.
OA SAT Reset
66.
SAT Temper Enable
67.
VAV With Thermostat
68.
VAV Control Offset
69.
FlexSys Dewpt Reset
70.
Exh Dmpr Pos For ON
71.
Exh Dmpr Pos For OFF
72.
OA Dmpr Pos For ON
73.
OA Dmpr Pos For OFF
74.
OAH Sensor Enable
75.
RAH Sensor Enable
76.
Exhaust Cntrl Offset
77.
Economizer Enable
78.
SAT Econo Loading
79.
Power Exhaust Enable
80.
OA Flow Cntrl Enable
81.
Comfort Vent Mode
82.
Cmfrt Vent Max Dampr
83.
IAQ Sensor Enable
84.
IAQ Sensor Span
85.
MAX DV Multiplier
86.
Altitude
87.
Morning Warm-Up
88.
Max Warm-Up Time
89.
Pre-Occupancy Purge
90.
Purge Schedule
91.
Purge OAT High Limit
92.
Purge OAT Low Limit
93.
Smoke Purge Mode
94.
Internal Clk/Sched
95.
Weekly Schedule
96.
Holiday Schedule
97.
Date and Time
NOTES FOR TABLE 7 – SETPOINTS AND VALUES
NOTES:
1. Both gas and electric heat are referred to functionally as "stepped"
heating or heating "stages"; both HW (hot water) and steam are
functionally referred to as "hydronic" heat.
JOHNSON CONTROLS
DEFAULT
UNITS
VALUE
ON
ON
°F
75°F
°F
45°F
°F
0°F
°F
0°F
inwg
3.00 inwg
OFF
OFF
OFF
ON
°F
4.5
OFF
%
80%
%
20%
%
60%
%
20%
OFF
OFF
inwg
0.015 inwg
ON
ON
OFF
OFF
OFF
%
75%
OFF
ppm
5000
1.25
Ft
1000
OFF
min
120 min
OFF
4am - 5am
all days
hh:mm start-end time
°F
85°
°F
55°
0
OFF
7am - 6pm
8 start/stop entries
weekdays
(No Sched)
(none)
2. The compressor runtimes and starts and fan runtimes are entered
only when a compressor or fan is replaced.
FORM 100.50-NOM7 (808)
VALUE
OCC
RANGE
KEY
ON or OFF
Unit Setup
ON or OFF
Unit Setup
0°-100°F
Unit Setup
45°-100°F
Unit Setup
0°/50°-80°F
Unit Setup
0°/70°-120°F
Unit Setup
0.00-5.00 inwg
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
2.0 – 6.0
Unit Setup
ON or OFF
Unit Setup
0-100%
Unit Setup
0-100%
Unit Setup
0-100%
Unit Setup
0-100%
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
0.010 – 0.050
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
ON or OFF
Unit Setup
0-100%
Unit Setup
ON or OFF
Unit Setup
0 – 10000
Unit Setup
1-2
Unit Setup
0-10000 Ft
Unit Setup
ON or OFF
Unit Setup
0-240 min
Unit Setup
ON or OFF
Unit Setup
Daily-Holiday
Unit Setup
0°-110°F
Unit Setup
0°-110°F
Unit Setup
0 – 5
Unit Setup
ON or OFF
Unit Setup
Unit Setup
16 entries
Unit Setup
dd-mm-year
Unit Status
hh:mm:ss am/pm
5 5
63