Fig. 12 - Occupied Heating And Cooling Setpoint Selection Algorithm - York J Series Manual

25 through 40 tons
Hide thumbs Also See for J Series:
Table of Contents

Advertisement

• The transition from cooling to occupied heating
occurs at 2°F below the "VAV Setpoint for SAT
reset".
• The reverse transition at 1.5°F below the "VAV
Setpoint for SAT reset". There is no "satisfied" or
"idle" state of the unit between cooling and oc-
cupied heating.
Enable VAV
Low Tem p.
Setpoint For
Cooling
Enable VAV
High T emp.
Setpoint For
Cooling
Enable VAV
Occupied
Hearing (If
-2.0 ˚ F
-1.5 ˚ F
-0.5 ˚ F
Allow e d)
SPA CE TEMPERA TURE
FIG. 12 – OCCUPIED HEATING AND COOLING
SETPOINT SELECTION ALGORITHM
Morning Warm Up
Morning Warm Up operation is carried out when:
• The Morning Warm Up parameter is ON.
• The Internal Clock/Schedule parameter is ON.
• Occupancy is scheduled for the current day.
JOHNSON CONTROLS
+2.0F
VAV Setpoint
For SAT Reset
LD06561
The Morning Warm Up start time will be 60 minutes
prior to scheduled occupancy, or BAS initiates the
morning warm-up.
When started, the Morning Warm Up operation is as
follows:
• Close economizer.
• Turn the Supply Fan ON and operate for 5 minutes
before beginning temperature control.
• For stepped heating:
• Control to maintain the RAT to the Morning
Warm Up Setpoint using the algorithm illus-
trated in Figure 12.
• For Hydronic heating:
• The SAT is controlled to the 2
Heat Setpoint.
• The VAV Relay output of the controller is set to
10 VAC during heating.
Morning Warm Up operation will end when:
• An occupancy (space is occupied) input is received
from the controller input.
• The scheduled occupancy time occurs.
• The Morning Warm Up operation times out based
on the Max Morning Warm Up Time parameter.