ETC Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Prepare for Installation
Echo Dual Tech Wall-mount Occupancy Sensors ship with electronics, a
decorator style wall plate, and a termination kit. The sensor may be installed
into an industry standard back box (provided by others) or surface mounted
back box (sold separately and available from ETC).
Compliance
cULus Listed
•
CE compliant
•
For use with ETC Echo Control Systems, powered by an Echo station power
supply.
Environment
Ambient
For indoor, commercial controls use only. Operating temperature 0-40°C
(32-104°F), humidity maximum 90% (non-condensing).
Location
ETC recommends paying special attention to the installation environment:
When operating in PIR only modes, the sensor must have an
•
unobstructed view of the room. Do not mount behind or near tall
cabinets, shelves, hanging light fixtures, etc.
Do not install the sensor within eight feet from an HVAC airflow
•
duct/vent.
Install the sensor where it cannot easily sense movement in areas
•
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms.
Note:
may allow for better occupancy detection results. See
page
7.
Dual Tech Wall-mount Occupancy Sensor
In areas of increased noise activity, enabling PIR only mode
Page 2 of 12
DIP Switches on
ETC