Settings
The Echo Dual Tech Wall-mount
Occupancy Sensor participates in an Echo
control system using the configured Space
and Address, which are selectable using
the rotary switches on the sensor
electronics located behind the removable
cover.
DIP switches and the [MODE] button, also
located on the sensor electronics, set the
sensor functionality and the occupancy
detection action when set to Basic
configuration mode. See
Note:
DIP switch 2 set to On, all other DIP switch and Mode button settings
are ignored.

Set Space and Address

Two rotary switches on the controller provide for assignment of the sensor
Space and Address. By default, these switches are set to Space 1, Address 1.
Commands are shared by all devices within a given space.
1. Set the Space rotary switch to the desired number (1 through 16) for
the space you want the sensor to control.
2. Set the Address rotary switch to desired address (1 through 16) for the
sensor identification in the selected space.
Note:
Dual Tech Wall-mount Occupancy Sensor
Configuration on page 8
When the sensor is placed into Custom configuration mode,
Do not duplicate a device Address within the same Space.
.