Unison Paradigm
Wall-mount Occupancy Sensor
Overview
The Paradigm Dual Tech Wall-mount Occupancy Sensor uses passive infrared
(PIR) technology and acoustic detection to provide reliable occupancy and
vacancy sensing for lighting control.
The wall-mount unit offers up to 140 degree field of detection with
optimized lens options to accommodate wide or narrow angle spaces. The
sensor is available in white, black, or cream finish.
Configuration
The Paradigm Architectural Control Processor (P-ACP) to which this Dual Tech
Wall-mount Occupancy Sensor is connected must learn, or be told, the
station hardware address (a.k.a. neuron ID). This ID (as labeled on the station)
can be manually entered into the configuration using LightDesigner software,
or it can be identified by the connected Paradigm ACP using the "Connect
Device" menu. See
Reference the Unison Paradigm Architectural Control Processor
Configuration Manual; specifically the section on Arch Setup Menu >
LonWorks Connections, or the reference Paradigm LightDesigner online help
system for related information to associate and connect the station to the
Paradigm control system.
®
Dual Tech
Wall-mount - Wide angle lens - coverage
• 60 ft (18.3 m) coverage at mounting height of 7-10
ft (2.1 - 3 m)
• 140 degree field of detection
Wall-mount - Narrow angle lens - coverage
• 16ft (4.9 m) by 75 ft (22.9 m) coverage at mounting
height of 6-7 ft (1.8 - 2.1 m)
• 40 degree field of detection
Sensor Coverage
Reference
Binding the Sensor to Paradigm
Corporate Headquarters
Service (Americas)
service@etcconnect.com
London, UK
Tel +44 (0)20 8896 1000
Rome, IT
Tel +39 (06) 32 111 683
Holzkirchen, DE
Tel +49 (80 24) 47 00-0
Hong Kong
Tel +852 2799 1220
Web:
etcconnect.com
© 2017 Electronic Theatre Controls, Inc.
specifications subject to change.
7184M2162
Rev A
Released 2017-05
on
Middleton, Wisconsin, USA
Service: (UK)
Service: (UK)

Service: (DE)
Service: (Asia)
ETC intends this document to be provided in its entirety.
page 7
.
page 5
on
.
Tel +608 831 4116
service@etceurope.com
service@etceurope.com
techserv-hoki@etcconnect.com
service@etcasia.com
Product information and

Advertisement

loading

Summary of Contents for ETC Unison Paradigm

  • Page 1 Service: (Asia) service@etcasia.com   Web: etcconnect.com © 2017 Electronic Theatre Controls, Inc. Product information and   specifications subject to change. ETC intends this document to be provided in its entirety.  7184M2162 Rev A Released 2017-05  ...
  • Page 2: Prepare For Installation

    Compliance • UL/cUL listed, complies with UL508A, UL916, and CSA C22.2 • CE compliant For use with ETC Paradigm Control Systems, powered by Paradigm Station Modules and/or Paradigm Station Repeater Modules. Environment Ambient For indoor, commercial controls use only. The sensors operate in ambient temperatures of -10°...
  • Page 3: Parts And Supplies

    Wall-mount Occupancy Sensors connect to the LinkConnect station communication bus. LinkConnect is a bidirectional protocol that uses one pair of wires (data+ and data-) for both data and power. ETC recommends using Belden 8471 (or approved equal) Class 2 wire. The total combined...
  • Page 4 ETC Installation Guide Dual Tech Wall-mount Occupancy Sensor The wall-mount sensor is provided with a mounting bracket with pre-routed LinkConnect pigtail wires. The sensor can be mounted to a switch box or finished wall surface. Pull the Belden 8471 (or equivalent) and one 14 AWG (2.5 mm ground wire to the mounting location (switch box or surface) and strip each wire 3/8”...
  • Page 5: Power Up And Test

    ETC Installation Guide Dual Tech Wall-mount Occupancy Sensor Attach the sensor head. a: Slide the removable cover off the sensor head. b: Route the three position connector with wiring pigtail through the sensor head. c: Loosen the set screw on the sensor retaining ring.
  • Page 6 ETC Installation Guide Dual Tech Wall-mount Occupancy Sensor • When occupancy in the space has only been triggered by acoustic detection for 60 minutes, acoustic detection is disabled until the next PIR detection event. PIR (only) Detection When acoustic detection is disabled, the following logic is used: •...
  • Page 7 ETC Installation Guide Dual Tech Wall-mount Occupancy Sensor Walk Test mode automatically exits and the sensor returns to normal operation after five minutes. You can also manually terminate by pressing the [Walk Test] button again. Verify Vacancy Operation For systems that have been configured for the installed sensor to control specific lighting circuits, Walk Test mode can also be used to verify vacancy operation.
  • Page 8 ETC Installation Guide Dual Tech Wall-mount Occupancy Sensor Wide Lens Top View 19.4° 19.4° (33ft) (33ft) (16ft) (16ft) 140° (16ft) (16ft) (33ft) (33ft) Side View 2.1m 2.1m (6.8ft) (6.8ft) 7.7 m 7.7 m 15.3m 15.3m 4.6m 4.6m 1.7m 1.7m (6ft)