ETC Installation Guide
Dual Tech Wall-mount Occupancy Sensor

DIP Switches

DIP switches on the sensor electronics provide for additional configuration
options including Use Custom Config, Vacancy Timeout, Enable/Disable
detection LEDs, PIR Only, and the ability to restore the sensor to its factory
defaults.
Switch #
1
2
3 and 4
5
6
7
8
Dual Tech Wall-mount Occupancy Sensor
Unused
Enable/Disable Custom Config Mode
When "Custom Config" is set to Off (also known as Basic
configuration mode), local DIP switch settings for Vacancy
Timeout, Enable PIR LED, and dual technology features are
used. Sensor actions can be adjusted using the program
[MODE] button. This is the default setting. See
Configuration on page 8
When "Custom Config" is set to On, all other local DIP
switch settings are ignored. Instead, the settings made by
the EchoAccess Mobile App are used.
Vacancy Timeout
5 min = Switches 3 and 4 are Off
15 min = Switch 3 is Off and Switch 4 is On (default)
30 min = Switch 3 is On and Switch 4 is Off
Auto = Both switches are On
Detection LEDs
When set to On (default), the occupancy detection LEDs
illuminate when movement is detected.
When set to Off, the occupancy detection LEDs are
disabled unless the unit is in Walk Test mode.
PIR Only Mode
When set to On, acoustic detection technology is disabled
for the sensor.
When set to Off (default), both PIR and acoustic detection
technologies are used by the sensor.
Unused
Restore to Defaults at boot
When set to On and power is cycled to the sensor, the
unit restores to its factory default settings.
Off is the default setting.