ETC Echoflex Elaho Dual Tech Wall-mount Vacancy Sensor Installation Manual
ETC Echoflex Elaho Dual Tech Wall-mount Vacancy Sensor Installation Manual

ETC Echoflex Elaho Dual Tech Wall-mount Vacancy Sensor Installation Manual

Advertisement

Quick Links

Echoflex Installation Guide
Elaho Dual Tech Wall-mount Vacancy Sensor
Overview
The Elaho Dual Tech Wall-mount Vacancy Sensor uses passive infrared
(PIR) technology and acoustic detection to provide reliable vacancy
sensing for lighting control. The sensor relies on local station control for
manual on and provides auto off functionality upon detection of vacancy.
Custom Configuration
This document guides you through the installation and local DIP switch
setup of the sensor. For more detailed information about custom
configuration options available using ElahoAccess, see the ElahoAccess
App integrated help system.
Note:
ElahoAccess, DIP switch 2 must be enabled. See
page 7.
Corporate Headquarters n Middleton, WI, USA | +1 608 831 4116
© 2023 Echoflex Solutions, Inc. | Trademark and patent info:
Web
echoflexsolutions.com
Third-party license agreement
change. Echoflex intends this document to be provided in its entirety.
8186M2186 Rev C Released 2023-06
The wall-mount unit offers up to 140 degree field
of detection with optimized lens options to
accommodate wide or narrow angle spaces.
Wall-mount - Wide Angle Lens - coverage
• 18.3 m (60 ft) at mounting height of
• 140 degree field of detection
Wall-mount - Narrow Angle Lens - coverage
• 4.9x22.9 m (16x75 ft) at mounting height of
• 40 degree field of detection
See
Sensor Coverage on page 11
To use the configuration settings applied using
| Email
info@echoflexsolutions.com
info: etcconnect.com/licenses
2.1–3 m (7–10 ft)
1.8–2.1 m (6–7 ft)
echoflexsolutions.com/ip
| Support
service@echoflexsolutions.com
| Product information and specifications subject to
.
DIP Switches on

Advertisement

Table of Contents
loading

Summary of Contents for ETC Echoflex Elaho Dual Tech Wall-mount Vacancy Sensor

  • Page 1 Echoflex Installation Guide Elaho Dual Tech Wall-mount Vacancy Sensor Overview The Elaho Dual Tech Wall-mount Vacancy Sensor uses passive infrared (PIR) technology and acoustic detection to provide reliable vacancy sensing for lighting control. The sensor relies on local station control for manual on and provides auto off functionality upon detection of vacancy.
  • Page 2: Prepare For Installation

    • When operating in PIR only modes, the sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets, shelves, hanging light fixtures, etc. • Do not install the sensor within eight feet from an HVAC airflow duct/vent.
  • Page 3: Wire Specification

    Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor Wire Specification The Dual Tech Wall-mount Vacancy Sensor connects to the EchoConnect communication bus. EchoConnect is a bi-directional protocol that uses one pair of wires (data+ and data–) for both data and power. Echoflex recommends using Belden 8471 Class 2 wire (or approved equal –...
  • Page 4: Installation

    Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor Installation Note: NEC Class 2 product to be wired in accordance to NEC Article 725 and local jurisdiction requirements. The wall-mount sensor is provided with a mounting bracket with pre- routed wires that can be mounted to a back box. Follow the detailed instructions for installation.
  • Page 5 Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor 4. Install the wall plate to the mounting plate. a. Align the top of the wall plate to the mounting plate, angling the bottom slightly. b. Hook the top of the wall plate to the tabs located on the mounting plate.
  • Page 6: Set Space And Address

    Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor Settings The Elaho Dual Tech Wall-mount Vacancy Sensor participates in an Elaho control system using the configured Space and Address, which are selectable using the rotary switches on the sensor electronics located behind the removable cover. MODE DIP switches, also located on the sensor electronics, set the sensor functionality.
  • Page 7: Dip Switches

    Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor DIP Switches DIP switches on the sensor electronics provide for additional configuration options including Use Custom Config, Vacancy Timeout, Enable/Disable detection LEDs, PIR Only Mode, and the ability to restore the sensor to its factory defaults. Switch # Unused (leave Off) Enable/Disable Custom Config Mode...
  • Page 8: Operation

    Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor Power Up All EchoConnect terminations in the system must be made before applying power to the system and sensor. When the sensor is powered, the PIR and acoustic detection LEDs illuminate for one minute for calibration and warm-up, and then return to normal operation according to the configuration.
  • Page 9: Vacancy Timeout

    Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor Custom When functionality other than Space Off is required, place the sensor in Custom configuration mode (DIP switch 2 set to On, the default setting). Customization of the sensor and all actions are configured using the ElahoAccess App.
  • Page 10 Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor Walk Test The sensor offers a Walk Test mode, which shortens the vacancy timer to 10 seconds and allows for simple and quick verification of the sensor’s coverage and range in the installed space. [Walk Test] button 1.
  • Page 11 Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor Sensor Coverage Narrow Lens Top View 77° (16 ft) 21.5° 14° 2.5 m 29° (8 ft) 6.56° 2.5 m (8 ft) (16 ft) Side View 2.1 m (6.8 ft) 10.7 m 18.3 m 30.5 m 2.2 m (3 ft)
  • Page 12 Echoflex Installation Guide Dual Tech Wall-mount Vacancy Sensor Wide Lens Top View 19.4° 10 m (33 ft) (16 ft) 140° (16 ft) 10 m (33 ft) Side View 2.1 m (6.8 ft) 7.7 m 4.6 m 15.3 m 1.7 m (6 ft) (15 ft) (25 ft)

Table of Contents