8.1 Parameters
Name
OutputConfiguration
Restore factory
settings
WriteProtect
SwitchingBit
FOU1
(1) Factory settings / on delivery
► After parameter setting connect the device again according to fig� 4�2 (→ 4.1)�
After removal of the write protection and correct integration of the IODD
(of the IO-Link device) the connected IO-Link device can be read and
configured by the IO-Link master�
Description
Selection between the automatic output configuration
(default) and the manual output configuration.
Default command to restore factory settings�
Write protection for the connected IO-Link device� If write
protection is active (parameter to 'on') write access of the
master is rejected by the data splitter�
Due to the system no feedback is given about rejected
write access to DPP (Direct Parameter Page →
IO-Link specification) nor about compatibility and validity
requests of actuator data by the master�
Removing write protection may jeopardise
the integrity of the application� Remove write
protection only after a thorough check of the
possible risks and effects�
Bit in the IO-Link process data flow representing the
switching output OUT1� The parameter is only available
if OutputConfiguration is set to 'manual'�
► For the position of the corresponding bit see
the IODD description (PDF) of the connected
IO-Link device�
Response of OUT1 in case of a fault� The parameter is
only available if OutputConfiguration is set to 'manual'�
(1)
auto
---
On
UK
0
Off
13