7 Parameter setting

Using an IO-Link capable parameter setting tool, the following options are
available:
- Reading current process values�
- Reading, changing and saving current parameter settings and transmitting
them to other units of the same type�
7.1 Adjustable parameters
Output function for OUT2:
OU2
Analogue signal: 4���20 mA [I] or 20���4 mA [Ineg]�
Analogue start value for temperature�
ASP
Measured value at which the output signal is 4 mA (20 mA at [OU2] = [Ineg]).
Analogue end value for temperature�
Measured value at which the output signal is 20 mA (4 mA at [OU2] = [Ineg]).
AEP
Minimum distance between ASP (analogue start point) and AEP (analogue end
point) = 5 °C or 9 °F.
Zero-point calibration�
COF
Setting range: ±10 °C in steps of 0.1 °C. The internal measured value "0" is
shifted by this value�
Behaviour of output 2 in case of an internal fault�
FOU2
- [On] = the analogue signal goes to the upper end stop value (21.0 mA).
- [OFF] = the analogue signal goes to the lower end stop value (3.5 mA.)