NORDAC FLEX (SK 200E ... SK 235E) – Brief instructions for Frequency Inverters
Pos : 675 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E013 [SK 200E ... SK 5xxE] @ 2\mod_1347454271218_14638.doc x @ 46752 @ @ 1
E013
13.0
Encoder error
13.1
Speed slip error
"Speed slip error"
13.2
Disconnect. control,
"Shut-down monitoring"
13.5
Reserved
13.6
Reserved
Pos : 676 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E014 "res erviert" [SK 200E ... SK 5xxE/SK 500P] @ 2\m od_1347454273854_14638.docx @ 46777 @ @ 1
---
Reserved
E014
Pos : 677 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E015 [SK 180E ... SK 5xxE] @ 2\mod_1347454278051_14638.doc x @ 46802 @ @ 1
E015
---
Reserved
Pos : 678 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E016 [SK 135E ... SK 5xxE, SK xxx E-FDS] @ 2\m od_1347454280625_14638.docx @ 46827 @ @ 1
E016
16.0
Motor phase error
16.1
Magn. Current Watch
"Magnetizing current
monitoring"
Pos : 679 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E018 "res erviert" [SK 2xx E/SK 5xxE/SK 2xx E-FDS, SK 500P] @ 44\m od_1594726433780_14638.docx @ 2645278 @ @ 1
18.0
Reserved
E018
Pos : 680 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E019 [SK 180E/SK 2x xE/SK 5xxE/SK2xxE-FD S, auß er SK 500P] @ 2\mod_1347454285788_14638.docx @ 46877 @ @ 1
E019
19.0
parameter ident.
"Parameter identification"
19.1
Star/delta incorrect
"Motor star/delta circuit
incorrect"
Pos : 681 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
84
No signal from encoder
Check 5 V sensor if available
Check supply voltage of encoder
The slip speed error limit was reached.
• Increase value in P327
The slip error monitoring was triggered; the motor could not
follow the setpoint.
Check motor data P201-P209! (important for current
controllers)
Check motor circuit
Check encoder settings P300 and following in servo
mode
Increase value for torque limit in P112
Increase value for current limit in P536
Check deceleration time P103 and extend if
necessary
Error message for POSICON  see supplementary manual
Error message for POSICON  see supplementary manual
Error message for POSICON  see supplementary manual
A motor phase is not connected.
Check P539
Check motor connection
Required exciting current not achieved at moment of switch-
on.
Check P539
Check motor connection
Error message for "Safe Pulse Block", see supplementary
instructions
Automatic identification of the connected motor was
unsuccessful
Check motor connection
Check preset motor data (P201 ... P209)
PMSM – CFC Closed Loop Operation: Rotor position
of motor incorrect in relation to incremental encoder
Determine rotor position (initial enable after a "Power
On" only with motor stationary) (P330)
BU 0240 en-US-4920