NORDAC FLEX (SK 200E ... SK 235E) – Brief instructions for Frequency Inverters
Pos : 293 /Anleitungen/El ektr onik /FU und Starter/5. Par ameter/Par ameterliste-Umrichter F unktionen_Ausw ahl [SK 2x xE_nur_BU 0240] @ 1\mod_1345717388031_14638.docx @ 39260 @ 55 @ 1
Parameter list - inverter functions (selection)
Parameter
Startup time (acceleration ramp) is the
time corresponding to the linear
P102
frequency rise from 0 Hz to the set
Acceleration time
maximum frequency (P105).
Deceleration time (deceleration ramp) is
the time corresponding to the linear
P103
frequency reduction from the set
Deceleration time
maximum frequency (P105) to 0 Hz.
The minimum frequency is the frequency
P104
supplied by the VFD as soon as it is
Minimum
enabled and no additional setpoint is
frequency
set.
If the frequency provided by the VFD
P105
after it has been enabled and the
Maximum
maximum setpoint value is available.
frequency
If a 4-pole NORD motor is used, the pre-
P200
set motor data can be called up.
Motor list
If a 4-pole NORD motor is not used, the
P201 – P208
motor data on the nameplate must be
Motor data
entered here.
The motor data is automatically
P220
determined by the VFD with this
Parameter
parameter.
identification
Definition of the functions of the various
setpoint inputs
Input selection:
Potentiometer P1 (P400, [-01]) -
SK 2x5E
P400
Potentiometer P2 (P400, [-02]) -
Function, setpoint
SK 2x5E
inputs
AIN1 (P400, [-01]) - SK 2x0E
AIN2 (P400, [-02]) - SK 2x0E
DIN 2 (P400, [-06])
DIN 3 (P400, [-07])
Definition of the functions of the various
digital inputs
Input selection:
P420
DIN 1 (P420, [-01])
Digital input
DIN 2 (P420, [-02])
functions
DIN 3 (P420, [-03])
DIN 4 (P420, [-04])
P428
Inverter enable with "Power On"
Automatic start
Definition of fixed frequency values
P465
Selection:
Fixed frequency/
Fixed frequency 1 (P465, [-01])
fixed array
Fixed frequency 2 (P465, [-02])
P509
Selection of the interface through which
Source control
the VFD is controlled.
word
Variable Frequency Drive is restored to
P523
the factory setting
Factory setting
72
Description
Factory
Settings/functions (selection)
setting
[2.00]
Note: Values < 0.1 must be avoided
[2.00]
Note: Values < 0.1 must be avoided
[0]
[50]
[0]
Select appropriate motor power
[xxx]
Data according to nameplate
01= stator resistor only
[0]
02 = motor identification
00 = no function
[xxx]
01 = setpoint frequency
15 = ramp time (P1/P2 only)
00 = no function
01 = enable right
02 = enable left
[xxx]
04 = fixed frequency 1
05 = fixed frequency 2
26= analog function 0-10 V
DIN2/3)
0: off (enable with flank)
1: on (enable with level)
[0]
Note: one digital input must be
programmed and set to enable!
[xxx]
00 = control terminals or keyboard
[0]
01 = only control terminals
03 = system bus
00 = no change
[0]
01= load factory setting
(only
BU 0240 en-US-4920