NORDAC FLEX (SK 200E ... SK 235E) – Brief instructions for Frequency Inverters
Information
The reaction time of a digital signal is approx. 4-5 ms and consists of the following:
For digital inputs DIN2 and DIN3 there is a parallel channel which relays the signal pulses between 250 Hz and
205 kHz directly to the processor, and therefore makes it possible for a rotary encoder to be evaluated.
Pos : 161 /Anleitungen/El ektr onik /FU und Starter/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/Informati on - Kabelführung @ 29\m od_1552045826996_14638.docx @ 2502097 @ @ 1
Information
Cable routing
All control cables (including PTC thermistors) must be routed separately from power and motor cables
to prevent interference in the device.
If the cables are routed in parallel, keep a minimum distance of 20 cm from cables which carry a
voltage of > 60 V. The minimum distance may be reduced by shielding live cables or by using
grounded metal separator within the cable ducts.
Alternatively: Use of a hybrid cable with shielded control lines.
Pos : 162 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
36
Reaction time of digital inputs
Scan time
Signal stability check
Internal processing
1 ms
3 ms
<
1 ms
BU 0240 en-US-4920