Table 8: Faq Operational Problems - Nord Drivesystems NORDAC FLEX SK 200E Series Brief Instructions

Frequency inverters
Hide thumbs Also See for NORDAC FLEX SK 200E Series:
Table of Contents

Advertisement

NORDAC FLEX (SK 200E ... SK 235E) – Brief instructions for Frequency Inverters
Pos : 713 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Betriebss tör ung en (Auflistung)/F AQ Betriebss tör ung en_07 [SK 2xx E] @ 9\m od_1448963477551_14638.docx @ 268672 @ @ 1
Motor speed does not
correspond to setpoint
Pos : 714 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Betriebss tör ung en (Auflistung)/F AQ Betriebss tör ung en_08 [SK 2xx E, SK 2xxE-FD S] @ 9\m od_1448963473878_14638.docx @ 268639 @ @ 1
Motor generating a
considerable amount of
noise (at the current limit)
and "OFF" signal is
implemented at slow speed
with little or no control,
possibly with error message
3.0
Pos : 715 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Betriebss tör ung en (Auflistung)/F AQ Betriebss tör ung en_09 [SK 1x 0E, SK 2xx E, SK 2xxE-FD S] @ 9\m od_1448963460429_14638.docx @ 268606 @ @ 1
Intermittent communication
error between VFD and
optional modules
Pos : 716 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Betriebss tör ung en (Auflistung)/F AQ Betriebss tör ung en_10_Tabellenuntersc hrift [SK 1xx E, SK 2x xE, SK x xxE-FD S] @ 9\m od_1448963453684_14638.docx @ 268573 @ @ 1

Table 8: FAQ operational problems

Pos : 718 /Anleitungen/El ektr onik /FU und Starter/7. T ec hnisc he D aten/!T echnisc he Daten (Ü bersc hrift) @ 0\m od_1328183045569_14638.docx @ 15174 @ 1 @ 1
90
Analog input function set to "Frequency
additions"
and
another
present
Tracks A and B swapped by encoder (for
speed feedback)
Incorrect encoder resolution setting
Encoder power supply missing
Encoder faulty
System bus terminating resistors
incorrectly set
Poor connection contact
Faults on system bus line
Maximum system bus length exceeded
Check P400
Check setting of integrated
setpoint
is
potentiometer (P1) (only
SK 2x5E)
P420, check active fixed
frequencies
Check bus setpoints
Check P104/P105 "min/max
frequency"
Check P113 "jog frequency"
Check encoder connections
Check P300, P301
Monitor via P735
Check encoder
First and last subscriber only:
set DIP switches for
terminating resistor
Check connections
Connect GND of all VFDs
connected to system bus
Pay attention to routing
regulations (separate routing
of signal and control cables
and power and motor cables)
Check cable lengths (system
bus)
BU 0240 en-US-4920

Advertisement

Table of Contents
loading

Table of Contents