NORDAC FLEX (SK 200E ... SK 235E) – Brief instructions for Frequency Inverters
Pos : 670 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E010 [SK 180E/SK 2x xE/SK2x xE-FD S] @ 40\mod_1575965968975_14638.docx @ 2581241 @ @ 1
E010
10.0
Bus timeout
10.2
Bus timeout option
10.4
Init error option
10.1
System error option
10.3
10.5
10.6
10.7
10.9
Module missing/P120
Pos : 671 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
82
(Telegram timeout/bus off 24 V int. CANbus
Data transfer is faulty. Check P513.
Check physical bus connections
Check bus protocol program process.
Check bus master.
Check 24 V supply of internal CAN/CANopen bus.
Node guarding error (internal CANopen)
Bus off error (internal CANbus)
Telegram timeout
Telegram transfer is faulty.
Check physical bus connections
Check bus protocol program process.
Check bus master.
PLC is in the "STOP" or "ERROR" state.
Initialization error in bus module
Check bus module current supply.
DIP switch setting of a connected I/O extension
module is incorrect
System error bus module
Further details can be found in the respective
additional bus instructions.
I/O extension:
Incorrect measurement of the input voltage or undefined
provision of the output voltage due to error in
reference voltage generation.
Short circuit at analog output
The module entered in parameter (P120) is not available.
Check connections
BU 0240 en-US-4920