E011
11.0
Control terminals
Pos : 673 /Anleitungen/El ektr onik /FU und Starter/6. M eldung en zum Betriebsz ustand/Störm eldung en (Auflistung)/F ehl er E012 [SK 180E/SK 2x xE/SK2x xE-FD S/SK 500P] @ 2\m od_1347454267926_14638.docx @ 46727 @ @ 1
E012
12.0
External watchdog
12.1
Limit moto./Customer
"Motor switch-off limit"
12.2
Limit gen.
"Generator switch-off limit"
12.3
Torque limit
12.4
Current limit
12.5
Load monitor
12.8
AI minimum,
"Analog In minimum"
12.9
AI maximum,
"Analog In maximum"
Pos : 674 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0240 en-US-4920
6 Operating status messages
A/D inverter error
Internal customer unit (internal data bus) faulty or damaged
by radio radiation (EMC)
•
Check control connections for short circuit.
•
Minimize EMC interference by laying control and power
cables separately.
•
Device and shielding must be well grounded.
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.
•
Check connections
•
Check setting P460
The drive switch-off limit (P534 [-01]) has triggered.
•
Reduce load on motor
•
Set higher value in (P534 [-01]).
The generator switch-off limit (P534 [-02]) has triggered.
•
Reduce load on motor
•
Set higher value in (P534 [-02]).
Limit from potentiometer or setpoint source has switched off.
P400 = 12
Limit from potentiometer or setpoint source has switched off.
P400 = 14
Switch-off due to overshooting or undershooting of
permissible load torques ((P525) ... (P529)) for the time set
in (P528).
•
Adjust load
•
Change limit values ((P525) ... (P527))
•
Increase delay time (P528)
•
Change monitoring mode (P529)
Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10 V with switch-off on error 1"
or "....2"
Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10 V with switch-off on
error 1" or "....2"
83