Pull Belden 8471 (or an equal type) control wiring and a 2.5 mm
Sensor IQ Breaker Panel through conduit.
2:
Strip 8 mm (5/16 in) of insulation from the ends of each wire pair.
3:
Remove the connector (J6) from the termination I/O board.
4:
Loosen the terminal screws for as many wire pairs as you are terminating.
5:
Insert each white wire (typical) from the pairs into the "+" terminal on the connector and tighten
the screws firmly to secure the wire into the connector.
6:
Insert each black wire (typical) from the pairs into the "-" terminal on the connector and tighten
the screws firmly to secure the wire into the connector.
7:
The 2.5 mm
• Connected between stations using WAGO Lever-Lock connectors (ETC part number J4166).
• Grounded to metal conduit.
• If grounded metal conduit is not installed, connect the ground wire to the Sensor IQ Breaker
Panel ground bus (same as the loads are grounded) and to the green/yellow striped wire
connected to the Echo Preset Station using a WAGO Lever-Lock connector. See the related
station installation instructions for details.
8:
Replace the EchoConnect connector to J6 on the termination I/O board.
Using Category 5 cable
When using EchoConnect over Cat5 cable, the bus uses all pairs in the Cat5 cable plus a separate
ESD ground wire. The combined length of an EchoConnect wire run using Cat5 cable cannot exceed
300 m (1000 ft).
To terminate Category 5 cable to the Sensor IQ Panel, you will need to use a EchoConnect Cat5 ERP
Termination Kit, ETC part number 7186A1208. Instructions for installation are provided with the kit.
Alternatively, manuals are available for free download on the ETC website etcconnect.com.
Installation
Enable only one EchoConnect power supply per system. See the
Processor Configuration Manual
disable the power supply. Enabling more than one power supply may interrupt
communication and cause undesirable results.
2
(14 AWG) ground wire can terminate in one of three ways:
, Station Power menu, for instructions to enable or
2
(14 AWG) ground into the
Power Control
35