Masonry Chimney Conversions - FireplaceXtrordinair 864 TV 40K Installation Manual

With ember-glo lights
Hide thumbs Also See for 864 TV 40K:
Table of Contents

Advertisement

28
Finalizing the Installation

Masonry Chimney Conversions

The vent may be adapted to utilize an existing masonry fireplace using the Duravent Co-Linear Adapter
(sku#96200328). The vent must be installed following all directions included with the vent and those listed below:
All requirements in the appliance
manual must be met. This
includes compliance with vent
configuration charts.
The restrictor position should be
set to the position that most
closely resembles the vent
configuration. NOTE: because
this installation utilizes non-
standard vent, the restrictor
position may vary. Carefully
monitor the burn characteristics to
verify correct restrictor position.
The UL gas liner must only be run
through the fireplace/chimney
(entire length of liner must be
retained within the
fireplace/chimney). Do not run
the liner near combustibles.
This appliance may utilize 6-5/8" diameter direct vent manufactured by Duravent (reducer may be required). The vent
may be adapted to utilize an existing masonry fireplace using the Duravent Masonry Chimney Conversion Kit (part #
46DVA-KMC). The vent must be installed following all directions included with the vent and those listed below:
NOTE: Before proceeding with the following installation example, check with the local building jurisdiction to
verify that this type of installation is allowed in your area.
All requirements in the appliance
manual must be met. This
includes compliance with vent
configuration charts.
The restrictor position should be
set to the position that most
closely resembles the vent
configuration. NOTE: because
this installation utilizes non-
standard vent, the restrictor
position may vary. Carefully
monitor the burn characteristics to
verify correct restrictor position.
The UL gas liner must only be run
through the fireplace/chimney
(entire length of liner must be
retained within the
fireplace/chimney). Do not run
the liner near combustibles.
© Travis Industries
(for qualified installers only)
4/23/2021 - 1480
864 40K Install

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents