Counter Functions - YASKAWA VIPA FM 050-1BB30 Manual

System slio counter module eco 2x32bit
Table of Contents

Advertisement

Deployment

Counter functions

MODE2_I/II C0/C1
Counter mode 2
MODE3_I/II C0/C1
Counter mode 3
4.4 Counter functions
Overview
52
Byte
Funktion
2
Input frequency C1 track A
3
Input frequency C1 track B
n
Input frequency allows you to preset a filter for I1, I4, I5 and I8. With the help of filters
you may e.g. filter signal peaks at a blurred input signal.
Byte
Bit 7 ... 0
0
n
Bit 2 ... 0: 0 (fix)
n
Bit 3: Count direction track B inverted
0 = No (not inverted)
1 = Yes (inverted)
n
Bit 7 ... 4: 0 (fix)
Byte
Bit 7 ... 0
0
n
Bit 2 ... 0: Signal evaluation
000b = Counter de-activated
001b = Rotary encoder single (at A and B)
010b = Rotary encoder double (at A and B)
011b = Rotary encoder quadruple (at A and B)
100b = Direction (pulse at A and direction at B)
Bit 7 ... 3: 0 (fix)
n
n
At de-activated counter the further parameter settings are ignored.
The counters of the 050-1BB30 are continuous counter, whose direction may be preset
by the parameterization. The counters serve e.g. for distance measuring with incremental
encoder. The activation res. de-activation of the counter happens via an internal gate (I
gate). The I gate corresponds to the software gate (SW gate). The SW gate is opened
(activated) via your user application by an edge 0-1 of the bit SW_GATE_SET of the con-
trol word in the output area. The software gate is closed (de-activated) by an edge 0-1 of
the bit SW_GATE_RESET. With an edge 0-1 at SW gate the counter is reset to 0. The
following states influence the I gate:
SW gate
0
1
with edge 0-1
VIPA System SLIO
Mögliche Werte
Other values are not permis-
sible!
influences I gate
0
1
1