Parameter Data - YASKAWA VIPA FM 050-1BB30 Manual

System slio counter module eco 2x32bit
Table of Contents

Advertisement

VIPA System SLIO

4.3 Parameter data

Parameter
Name
Bytes
CH0A
1
CH1B
1
CH2A
1
CH3B
1
MODE2_I
1
MODE3_I
1
MODE2_II
1
MODE3_II
1
1) This parameter may only be transferred at STOP state.
CHxx Input frequency
HB300 | FM | 050-1BB30 | en | 20-40
Bit
Name
6
RES_SET
7 ... 9
-
10
SW_GATE_RESET
11 ... 15
-
Via parameterization you may define among others:
n
Input filter
n
Counter operating mode res. behavior
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 3100h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Function
C0: Input frequency track A
C0: Input frequency track B
C1: Input frequency track A
C1: Input frequency track B
1
C0: Counter mode 2
1
C0: Counter mode 3
1
C1: Counter mode 2
1
C1: Counter mode 3
Byte
Funktion
0
Input frequency C0 track A
1
Input frequency C0 track B
Function
resets the bits
STS_OFLW, STS_UFLW
and STS_ZP edge 0-1
reserved
resets the software gate
reserved
Default
DS
02h
01h
02h
01h
02h
01h
02h
01h
00h
80h
00h
80h
00h
82h
00h
82h
Mögliche Werte
n
02h: 100kHz
n
03h: 60kHz
n
04h: 30kHz
n
06h: 10kHz
n
07h: 5kHz
n
08h: 2kHz
n
09h: 1kHz
Deployment
Parameter data
IX
SX
3100h
01h
3101h
02h
3102h
03h
3103h
04h
3104h
05h
3105h
06h
3106h
07h
3107h
08h
51

Advertisement

Table of Contents
loading